DCA-180SSK — GENERATOR START-UP PROCEDURE (MANUAL)

17.The tachometer (Figure 50) will indicate the speed of the engine when the generator is operating. Under normal operating conditions this speed should be approximately 1800 RPM’s.

21.Observe he generator's ammeter (Figure 53) and verify that it reads the anticipated amount of current with respect to the load. Remember the ammeter will only display a current reading if the load is in use.

40

2060

075

A

Figure 50. Engine Tachometer

18.If the engine speed is too high or low, use the high idle adjust trimmer (Figure 51) located on the control box to adjust the rated speed of the engine

Figure 51. Engine Idle Adjust Trimmer

19.After the engine has been running for a few minutes, look at the status LED’S on the "MPEC" display (Figure

41)and check it for any abnormal conditions. If any abnormal conditions exist, take corrective action to solve the problem.

20.If there are no abnormal problems shown on the “MPEC" LED display, turn the MAIN, GFCI and LOAD circuit breakers to their ON position (Figure 52).

Figure 53. Ammeter (Load)

22.The generator will run until manually stopped or an abnormal condition occurs.

Figure 52. Main and GFCI Circuit Breakers

DCA-180SSK — PARTS AND OPERATION MANUAL— REV. #3 (06/11/09) — PAGE 51

Page 51
Image 51
Multiquip DCA180SSK manual Engine Tachometer

DCA180SSK specifications

The Multiquip DCA180SSK is a powerful and versatile generator specifically designed for construction sites, events, and other demanding applications. This model boasts an impressive power output of 180 kVA, making it suitable for a wide range of electrical needs. Its reliable performance combined with advanced features makes it a preferred choice for professionals in various industries.

One of the standout characteristics of the DCA180SSK is its robust, diesel-powered engine. This generator is equipped with a reliable Yanmar diesel engine, known for its durability and efficiency. The engine not only ensures consistent power delivery but also meets stringent emission regulations, making it environmentally friendly. The unit features a fuel-efficient design capable of running for extended periods, which reduces the frequency of refueling and associated downtime.

The DCA180SSK generator is also engineered for ease of use. It incorporates a user-friendly control panel that provides clear visibility of operational parameters, including voltage output, frequency, and fuel levels. This intuitive interface allows operators to monitor the generator’s performance effortlessly.

Another significant technological advancement in the DCA180SSK is its advanced sound attenuation features. The generator is built within a durable, weather-protective enclosure that minimizes noise levels to enhance worksite safety and compliance with local regulations. This feature not only benefits job sites in urban environments but also improves working conditions for operators and workers alike.

Portability is another key attribute. The DCA180SSK is designed with a compact structure, making it easy to transport and position on-site. The addition of lifting points facilitates quick and safe relocation, while its rugged chassis ensures it can withstand the rigors of construction environments.

This generator also incorporates numerous safety features, including automatic shut-off protocols for low oil pressure and high temperature, enhancing operator safety and extending engine life. With its blend of technology, durability, and user-centric design, the Multiquip DCA180SSK generator provides dependable power for any demanding application, ensuring that work proceeds smoothly, efficiently, and safely.