Multiquip EGC1000C Alternator Specifications, Engine Specifications, Amperage, Exhaust System

Models: EGC1000C

1 4
Download 4 pages 9.97 Kb
Page 2
Image 2
Alternator Specifications

1000 kW Containerized Diesel Generator Set

Alternator Specifications

Model 741RSL4045

Marathon Magna Max

Type

Rotating Field

Number of Leads

10 or 12

Generator Type

Rotating Field; PMG

Voltage Regulator

Solid State, Digital, Model DVR2000

Insulation

NEMA MG1-1.66

Material

Class H

Temperature Rise

105o / 125o C

Bearing: Number, Type

Single Sealed

Coupling

Flexible Disk

Amortisseur Windings

Full

Voltage Regulation

0.25%

One Step Load Acceptance

100

% of rating per NFPA-110

 

Peak Motor Starting HP

500

Generator Efficiency at Full Load

95%

Phase Sequence

ABC (L1, L2, L3)

L-L Harmonic Max Total

5.0%

L-L Harmonic Max Single

3.0%

Voltage Dip Upon Full Load Application (1 Step)

20% for 1.6 sec.

Voltage Rise Upon Full Load Rejection (1 Step)

10% for 0.6 sec.

The 1000kW Sound Attenuated Generator includes a reconnectable 4, 10 or 12 lead generator that may be configured for any standard 60 Hz out voltage.

Alternator Features

All ratings tested per MIL-STD-705 as applicable

Protection for overload and short circuit

Designed and built within NEMA, IEEE and ANSI standards for temperature rise

PMG exciter for superior regulation and response

Three-phase sensing on regulator with EMI protection

Skewed rotor for smooth voltage wave form

Vacuum impregnated epoxy varnish - Fungus resistant per MIL-I-24092

Sustain short circuit current at 300% of rated current up to 10 seconds

Listed to UL1446 and UL1004B Standards

Engine Specifications

EPA Engine Family Name CEXL030.AAD

Cummins QST30-G5

Engine Type

4-cycle, Turbocharged, Aftercooled

Cylinder Arrangement

V-12

Displacement

1860 cu in (30.5 L)

Bore

5.51 in. (140 mm)

Stroke

6.50 in. (165 mm)

Compression Ratio

14.0:1

Piston Speed (60Hz)

32.4 ft/sec. @ 60 Hz

Bearing Main: Number

7

Bearing Main: Type

Replaceable, precision

Cylinder Head Material

Cast iron

Crankshaft Material

Forged steel

Brake Mean Effective Pressure (BMEP)

352 psi (2,427 kPa)

Rated RPM (60Hz)

1800 RPM

Max. Power At Rated RPM (with fan)

1490 hp (1112 kW)

Governor: Type; Make/Model

Electronic

Frequency Regulation:

±0.25%

No load to full load

 

Frequency Regulation:

Isochronous under varying loads

Steady State

from no load to 100% rated load

Air Cleaner Type - All Models

Dry

 

 

Amperage

Voltage

Phase

Power

Amperes

 

Factor

Standby

 

Prime

 

 

 

120/208

3

0.8

3200

 

3200

277/480

3

0.8

1504

 

1353

Engine Electrical System

Battery Charging Alternator Ground Type

Negative

Volts

24 VDC

Ampere Rating

35A

Starter Motor Rated Voltage

24 VDC

Minimum Recommended Battery for

1280 CCA

0 °C / Cold Cranking Performance

 

Exhaust System

Exhaust Temperature at Rated kW (Dry Exhaust)

975oF (524oC)

Exhaust Flow at Rated kW (Standby)

7775 cfm (220 m3/min)

Silencer Type

Critical grade

Maximum Allowable Backpressure

27 in/H2O (6.7 kPa)

Exhaust Outlet Diameter

10 in.

 

 

EGC1000C Rev 3

Page 2
Image 2
Multiquip EGC1000C Alternator Specifications, Engine Specifications, Amperage, Exhaust System, Engine Electrical System