troubleshooting (GENERATOR)

Table 7. Generator Troubleshooting

Symptom

Possible Problem

Solution

Low voltage

Engine speed too low?

Raise engine speed to rated RPM.

 

AC voltmeter not working?

Replace Ac voltmeter.

 

Control box internal wiring

Check control box wiring.

 

malfunction?

 

 

Low voltage. Engine speed normal

Defective ignition coil?

Check red and green ignition wires.

Replace ignition wires if necessary.

 

3650 RPM (unloaded), 2500 RPM

 

 

Rotor winding malfunction?

Check or replace rotor.

(idle)

Stator winding malfunction?

Check or replace stator.

 

 

Leakage breaker malfunction?

Check or replace CB1.

 

Full power switch malfunction?

Check full power switch and full power

 

switch circuit.

 

 

Voltage output too high.

Engine speed too high?

Lower engine speed to rated RPM.

Voltage output too high. Engine speed

Control box internal wiring

Check control box wiring.

normal 3650 RPM (unloaded), 2500

malfunction

RPM (idle)

 

 

 

Circuit breaker will not turn on "NO

Defective circuit breaker?

Replace circuit breaker.

LOAD"

 

 

Circuit breaker will turn on "LOADED"

Overload Condition?

Reduce load or replace breaker.

 

 

but trips immediately.

Load circuit is shorted?

Check load circuit for short.

 

 

 

Does not accelerate from low to high

Stuck solenoid?

Check solenoid.

"NO LOAD"

Bad Idle control switch?

Check or replace idle control switch.

Does not accelerate from low to high

Idle control switch malfunction?

Check or replace idle control switch.

Idle control device malfunction?

Check or replace idle control device.

"LOAD ACTIVE"

Control box interal wiring defective?

Check control box wiring.

 

 

Defective rotor windings?

Check or replace rotor.

Does not decelerate no"VOLTAGE

Defective solenoid?

Check or replace solenoid.

OUTPUT".

Defective idle control device?

Check or replace idle control device.

 

Defective solenoid?

Check or replace idle control device.

 

Control box wiring malfunction?

Check control box wiring, replace any

Does not decelerate but has

defective components.

 

"VOLTAGE OUTPUT".

Defective solenoid?

Check or replace solenoid.

 

Idle control device malfunction?

Check or replace idle control device.

page 32 — GA9.7HE 60 hz gENERATOR• operation and parts manual — rev. #1 (04/29/10)

Page 32
Image 32
Multiquip ga-9.7HE manual Troubleshooting Generator

ga-9.7HE specifications

The Multiquip GA-9.7HE is a high-performance generator that caters to the diverse needs of construction sites, industrial applications, and outdoor events. Engineered with robust features and advanced technologies, it stands out as a reliable power source in various environments.

One of the standout features of the GA-9.7HE is its powerful engine. Powered by a Honda gasoline engine, this generator delivers an impressive output of 9.7 kW, making it suitable for powering multiple tools and equipment simultaneously. The engine is designed for efficiency and durability, ensuring long operational hours with minimal maintenance requirements.

An integral component of the GA-9.7HE is its advanced inverter technology. This technology allows for cleaner, stable power output that is ideal for sensitive electronics and equipment. Whether it's powering construction tools or providing backup for electronics at an outdoor event, the inverter capability ensures optimal performance without risking damage to sensitive devices.

Additionally, the GA-9.7HE features a user-friendly control panel that provides easy access to essential functions. The control panel includes circuit breakers, output indicators, and start/stop controls, allowing operators to manage the generator efficiently. This ease of use is critical for ensuring seamless operation, especially in fast-paced work environments.

Portability is another key aspect of the GA-9.7HE. It is designed with a compact frame and comes equipped with heavy-duty wheels, making it easy to transport across job sites or during events. The lightweight construction also contributes to its mobility, allowing users to quickly reposition the generator as needed.

Safety features have not been overlooked in the GA-9.7HE. It includes automatic low-oil shutdown and circuit breaker protection, which help prevent engine damage and electrical issues. These safety measures are essential for maintaining the longevity of the generator and ensuring safe operation in various applications.

With a focus on reliability, efficiency, and versatility, the Multiquip GA-9.7HE is an excellent choice for those seeking a dependable power solution. Its combination of a powerful engine, advanced inverter technology, user-friendly design, and safety features makes it a valuable asset for contractors, event planners, and anyone in need of portable power.