N-TRON SWITCH GROUNDING TECHNIQUES
The grounding philosophy of any control system is an integral part of the design. N-Tron swit ches are designed
to be g rounded, but the user h as been giv en the flexi bility to floa t the swit ch when r equired. The best noise
immunity and emissions (i.e. CE) are obtained when the N-Tron switch chassis is connected to earth ground via
a drain wire. Some N-Tron switches h ave metal din-rail brackets that can ground the switch if the din-rail is
grounded. In some cases, N-Tron switches with metal b rackets can be supplied with optional plastic brackets if
isolation is required.
Both V- legs of the power input connec tor are connected to
chassis internally on the PCB. Connecting a drain wire to
earth ground from one of t he V- terminal plugs as shown here
will ground the switch and the chassis. The power leads from
the power source should be limited to 3 meters or less in
length.
As an alternate, users can run a drain wi re & lug from any of the Din-Rail
screws or empty PEM nuts on the enclosure. When using an unused PEM
nut to connect a ground lug via a machine screw, care should be taken to
limit the penetration of the outer skin by less than 1/4 in. Failure to do so
may cause irreversible damage to the internal components of the switch.
Note: Before applying power to the grounded switch, you must use a volt
meter to verify there is no voltage difference between the power supply’s
negative output terminal and the switch chassis grounding point.
The use of shielded cables between devices is not required for most N-Tron devices (please consult the user
manuals for specific d etails). If the use of shielded cables is required, it is generally recommended to only
connect the shield at one end t o prevent ground l oops and interfere with low level sig nals (i.e. thermocouples,
RTD, etc.). Cat5e cables manufactured to EIA-568A or 568B specifications are required for use with N-Tron
Switches.
In the event all Cat5e patch c able distances are small (i.e. All Ethe rnet devices are located the same local
cabinet and/or referenced to the same earth ground), it is permissible to use fully shielded cables terminated to
chassis ground at both ends in systems void of low level analog signals.