Napoleon Fireplaces BGD40-P, BGD40-N manual Fireplace Vent Connection, GAS Installation

Models: BGD40-P BGD40-N

1 36
Download 36 pages 35.09 Kb
Page 21
Image 21
MANUAL SHUT-OFF VALVE

6. Aligning the seams of the

terminal and air terminal connector,

21

FIREPLACE VENT CONNECTION

place the terminal over the air

terminal connector making sure

the liner goes into the hole in the

terminal. Secure with the three

screws provided.

7. Apply a heavy bead of

weatherproof caulking 2"

above the fl ashing. NOTE:

Maintain a minimum 2” space

between the air inlet base

and the storm collar. Install

the storm collar around the

air terminal and slide downFIGURE 40 to the caulking. Tighten to

ensure that a weather-tight seal between the air terminal and the collar is achieved.

1.Install the 5" diameter flex pipe to the fi replace. Secure with 3 screws and fl at washers. Seal the joint and screw holes using high temp sealant

(not supplied) or Red RTV Silicone may also be used in this location.

2.Install the 8" diam-

eter fl ex pipe to the

replace. Attach and seal the joints.

For optimum per-

formance it is recommended that all horizontal ¼" rise per foot.

FIGURE 41

runs have a

GAS INSTALLATION

Proceed once the vent installation is complete.

NOTE: All gas connections must be contained within the fireplace when complete.

1.Move the fi replace into position and secure to the fl oor through the 1/4" holes located at either side of the base.

2.The fi replace is designed to accept 3/8" gas supply line.

3.Connect the gas supply in accordance to local codes. In the absence thereof, install according to the National Installation Code.

4.When fl exing any gas line, support the gas valve so that the lines are not bent

or kinked.

5. Check for gas leaks by brushing on a soap and water solution.

L

O

DO NOT USE OPEN FLAME.

HI

Purge all gas lines with the glass door open. Assure that a continuous gas flow is at

P

the burner before closing the door.

TOLI

 

FIGURE 42

 

O

N

F

F

O

P

I

TOL

 

CERTIFIEDUNDER / HOMOLOGUE SELON LES NORMES: CSA 2.33-2002, ANSI Z21.88-2002 VENTED GAS FIREPLACE HEATER / FOYER DE CHAUFFAGE AU GAZ AVEC EVACUATION

DIRECT VENT GAS FIREPLACE.APPROVED FOR BEDROOM, BATHROOM AND BED-SITTING ROOM INSTALLATION. SUITABLE FOR MOBILE HOME INSTALLATION IF INSTALLED IN ACCORDANCE WITH THE CURRENT STANDARD CAN/CSAZ240MH SERIES GAS EQUIPPED MOBILE HOMES, IN CANADA OR IN THE UNITED STATES THE MANUFACTURED HOME CONTRUCTION AND SAFETY STANDARD,TITLE 24 CFR, PART 3280. WHENTHIS US STANDARD IS NOTAPPLICABLE USETHE STANDARD FOR FIRE SAFETY CRITERIA FOR MANUFACTURED HOME INSTALLATIONS,SITESAND COMMUNITIES, ANSI/ NFPA501A. FOYER A GAZ VENTILE DIRECT. HOMOLOGUE POUR INSTALLATION DANS UNE CHAMBRE A COUCHER, UNE SALLE DE BAIN ET UN STUDIO. APPROPRIE POUR INSTALLATION DANS UNE MAISON MOBILE SI SON INSTALLATION CONFORME AUX EXIGENCES DE LA NORME CAN/CSA Z240MH SERIE DE MAISONS MOBILES EQUIPEES AU GAZ, EN VIGUEUR AU CANADA OU AUX ETATS-UNIS DE LA NORME DE SECURITE ET DE CONSTRUCTION DE MAISONS MANUFACTUREES,TITRE 24 CFR, SECTION 3280. DANS LE CAS OU CETTE NORME D'ETATS-UNIS NE PEUT ETRE APPLIQUEE, SE REFERERA LA NORME RELATIVE AU CRITERE DE MESURES DE SECURITE CONTRE L'INCENDIE POUR LES INSTALLATIONS DANS LES MAISONS MANUFACTURES, LES SITES ET LES COMMUNAUTES, ANSI/NFPA 501A.

MODEL BGD40 - N

ALTITUDE/ELEVATION:

0-4500FT(0-1370m)

MODELBCDV400-N

INPUT/ALIMENTATION:

30,000 BTU/h

REDUCED INPUT/ALIMENTATION REDUIT:

 

 

20,000 BTU/h

 

ORIFICE:

#39

MANIFOLD PRESSURE: 3.5" WATER COLUMN

PRESSION AU COLLECTEUR: 3.5" D'UNE COLONNE D'EAU

MINIMUM SUPPLY PRESSURE: 4.5" WATER COLUMN

PRESSION D'ALIMENTATION MINIMALE: 4.5" D'UNE COLONNE D'EAU

MAXIMUM SUPPLY PRESSURE: 7.0" WATER COLUMN

PRESSION D'ALIMENTATION MAXIMAL: 7.0" D'UNE COLONNE D'EAU

 

 

ALTITUDE / ELEVATION:

0-4500FT (0-1370m)

MODEL BGD40 - P

 

 

 

 

INPUT /ALIMENTATION:

 

30,000 BTU/h

MODELBCDV400-P

 

 

 

 

REDUCED INPUT / ALIMENTATION REDUIT:

 

 

 

 

 

 

 

 

 

20,000 BTU/h

 

 

 

 

 

ORIFICE:

 

#52

 

 

 

REFERENCE #15510

 

 

MANIFOLD PRESSURE: 10" WATER COLUMN

 

 

PRESSION AU COLLECTEUR: 10" D'UNE COLONNE D'EAU

CERTIFIEDFORCANADA AND USA

 

MINIMUM SUPPLY PRESSURE: 11" WATER COLUMN

CERTIFIEEPOUR

ET

PRESSION D'ALIMENTATION MINIMALE: 11" D'UNE COLONNE D'EAU

MAXIMUM SUPPLY PRESSURE: 13" WATER COLUMN

PRESSION D'ALIMENTATION MAXIMAL: 13" D'UNE COLONNE D'EAU

NOT FOR USE WITH SOLID FUEL. FOR USE WITH COVERS AND

UN COMBUSTIBLE SOLIDE NE DOIT PAS ETRE UTILISE AVEC CET

GLASS DOORS CERTIFIED WITH THIS UNIT ONLY.

 

APPAREIL. UTILISER AVEC LES COUVERTURES ET LES PORTES

WARNING:DO NOT ADD ANY MATERIAL TO THE APPLIANCE, WHICH WILL COME IN CONTACT

VITREES HOMOLOGUEES SEULEMENT AVEC CETTE UNITE.

WITHTHE FLAMES, OTHER THAN THAT SUPPLIED BY THE MANUFACTURER WITHTHE APPLIANCE.

AVERTISSEMENT: N'AJOUTEZ PAS A CET APPAREIL AUCUN MATERIAU DEVANT ENTRER EN

MINIMUM CLEARANCE TO COMBUSTIBLE MATERIALS /

 

 

CONTACT AVEC LES FLAMMES AUTRE QUE CELUI QUI EST FOURNI AVEC CET APPAREIL PAR LE

DEGAGEMENTS MINIMAUX DES MATERIAUX COMBUSTIBLES:

 

 

FABRICANT.

 

 

TOP, FLOOR, SIDES & BACK

0

THEAPPLIANCE MUST BE VENTED USING THEAPPROPRIATE WOLF STEEL VENT KITS. SEE OWNERS

INSTALLATION MANUAL FOR VENTING SPECIFICS. PROPER REINSTALLATION AND RESEALING IS

DESSUS, PLANCHER, COTES & ARRIERE

NECESSARY AFTER SERVICING THE VENT-AIR INTAKE SYSTEM.

RECESSED DEPTH (CORNER INSTALLATION ONLY)

PROFONDEUR D'ENCASTRE (INSTALLATION DU COIN SEULEMENT)

VENT / EVENT

25¼"

1"

L'APPAREIL DOIT EVACUER SES GAZ EN UTILISANT L'ENSEMBLE D'EVACUATION PROPRE A WOLF STEEL. REFERER AUMANUEL D'INSTALLATION DE PROPRIETAIRE POUR L'EVACUATION PRECISE. IL ESTIMPORTANT DE BIEN REINSTALLERET RESCELLER L'EVENT APRESAVOIR ASSURE LE MAINTIEN DU SYSTEME DE PRISE D'AIR.

MANTLE HEIGHT / HAUTEUR DU MANTEAU

5"*

*MAXIMUM HORIZONTAL EXTENSION / L'EXTENSION HORIZONTALE MAXIMALE: 3". SEE INSTRUC- TION MANUAL FOR GREATER EXTENSIONS. REFERER AU MANUEL D'INSTRUCTION POUR DES EXTENSIONS PLUS GRANDES.

MINIMUM AND MAXIMUM HORIZONTAL VENT LENGTHS ARE 10 INCHES AND 20 FEET RESPEC- TIVELY. LES LONGUEURS HORIZONTALES MINIMALE ET MAXIMALE SONT 10 POUCES ET 20 PIEDS RESPECTIVEMENT.

WOLF STEEL LTD, BARRIE, ON, CANADA

ELECTRICAL RATING / CLASSIFICATION: 115V, 0.82AMP, 60HZ

OPTIONAL FAN KIT / ENSEMBLE DE VENTILATEUR FACULTATIF: GZ-550KT

MADE IN CANADA / FABRIQUE AU CANADA

SERIAL NUMBER/NO. DE SERIE: BGD40 / BCDV400

 

GD22

W385-0249

FIGURE 42

W415-0299 / J / 04.14.08

Page 21
Image 21
Napoleon Fireplaces BGD40-P, BGD40-N manual Fireplace Vent Connection, GAS Installation