15
USING FLEXIBLE VENT COMPONENTS
FIGURE 20
ELBOW
Do not allow the inside liner to bunch up on horizontal or vertical runs and elbows. Keep it pulled tight. A 1 1/4" air gap between the inner liner and the outer liner all around is
SPACERS required for safe operation. A spacer is required at the start, middle and end of each elbow to ensure this gap
is maintained.
For safe and proper operation of the fireplace, fol- low the venting instructions exactly.
2.Stretch the 5" diameter flexible liner to the required length. Slip the liner a minimum of 2" over the inner sleeve of the air terminal connector and secure with 3 #8 screws. Seal using a heavy bead of the high temperature sealant.
3.Repeat using 8" diameter fl exible
liner.
4.Thread the air terminal connector/
pipe assembly down through the roof. The air terminal must be located vertically and plumb. Attach the air terminal connector to the roof sup-
FIGURE 22
FIGURE 23
All inner exhaust and outer intake vent pipe joints may be sealed using either Red RTV high temp silicone sealant or Black high temp Mill
Pac with the exception of the fireplace exhaust flue collar which must be sealed using Mill Pac (not supplied).
Use only approved flexible liner kits marked:
"Wolf Steel Approved Venting" as identified by the stamp only on the 8” outer liner.
For safe and proper operation of the fireplace, follow the venting instructions exactly.
NOTE: Eight (8”) inches is the minimum bend radius allowed for the 8” diameter fl exible liner.
HORIZONTAL AIR TERMINAL INSTALLATION
1.Secure the terminal to the terminal extension plate (see figure
21).
2.Stretch the 5" diameter fl exible liner to the required length tak- ing into account the additional length needed for the fi nished wall surface. Slip the liner a minimum of 2" over the inner sleeve of the
air terminal and secure with
3 #8 screws. Apply a heavy |
| CAULKING |
|
|
|
|
|
| |
bead of the high tempera- | #10x2½" |
|
|
|
ture sealant |
|
|
| |
SCREWS | CAULKING |
| ||
|
| |||
(not supplied). |
|
| 5"FLEX | |
3. Using the 8" diameter |
|
| ||
|
| PIPE | ||
|
|
|
| |
fl exible liner, slide over the |
|
|
| 8" FLEX |
outer combustion air sleeve |
| 2" | OVERLAP | PIPE |
|
|
|
| |
of the air terminal and se- |
|
|
|
|
cure with 3 #8 screws. Seal |
|
|
| |
| TERMINAL | SEALANT |
| |
as before. |
| FIGURE 21 | ||
| EXTENSION | |||
| PLATE |
The air terminal mounting plate may be recessed
into the exterior wall or siding by 1½", the depth of the return flange.
4.Insert the liners through the fi restop maintaining the required clearance to combustibles. Holding the air terminal (lettering in an upright, readable position), secure to the exterior wall and make weather tight by sealing with caulking (not supplied).
5.Apply a heavy bead of the high temperature sealant,
6.Using the 8" diameter fl exible aluminium liner, apply high tempera- ture sealant
VERTICAL AIR TERMINAL INSTALLATION
1.Fasten the roof support to the roof using the screws provided. The roof support is optional. In this case the venting is to be adequately supported using either an alternate method suitable to the authority having jurisdiction or the optional roof support.
port, ensuring that a minimum 16" of air terminal will penetrate the roof when fastened.
DO NOT CLAMP THE FLEXIBLE ALU-
MINIUM LINER.
5.Remove nails from the shingles, above and to the sides of the chimney. Place the fl ashing over the air terminal and slide it underneath the sides and upper edge of the shingles. Ensure
that the air terminal connector is properly centred within the fl ashing, giving a 3/4" margin all around. Fasten to the roof. Do not nail through the lower portion of the fl ashing. Make
6.Aligning the seams of the terminal and air terminal connector, place the terminal over the air terminal connector making sure the liner goes into the hole in the terminal. Secure screws provided.
7. Apply a heavy bead of weather- | FIGURE 24 |
proof caulking 2" above the fl ashing. |
|
Note: Maintain a minimum 2" space |
|
between the air inlet base and the storm |
|
collar. Install the storm collar around the |
|
air terminal and slide down to the caulk- |
|
ing. Tighten to ensure that a weather- |
|
tight seal between the air terminal and |
|
the collar is achieved. |
|
8.If more liner needs to be used to reach the fireplace, couple them together
as illustrated in Figure 25. The vent system must be supported ap- proximately every 3 feet for both vertical and horizontal runs. Use noncombustible strapping to maintain a clearance to combustibles of 1".
FIGURE 25
FIREPLACE VENT CONNECTION
1. Install the 5" diameter |
| |
fl exible liner to the fi replace. |
| |
Secure with 3 screws and flat |
| |
washers. Seal the joint and |
| |
screw holes using the high |
| |
temperature sealant W573- |
| |
0007 (not supplied). |
| |
2. Install the 8" diameter |
| |
fl exible liner to the fi replace. | FIGURE 26 | |
Attach and seal with high | ||
| ||
temperature sealant |
| |
|