Napoleon Fireplaces BGDV42N, BGDV42P manual Horizontal Termination, Formula 1 HT 4.2 VT

Models: BGDV42P BGDV42N

1 28
Download 28 pages 48.65 Kb
Page 10
Image 10
Formula 1: HT < 4.2 VT

10

HORIZONTAL TERMINATION

when (HT) > (VT)

Example 2:

Simple venting configuration (only one 45º and 90° elbow)

 

See graph to determine the re-

 

 

 

90°

FIGURE 7

FIGURE 8

 

90°

quired vertical rise VT for the re-

 

 

 

 

H4

quired horizontal run HT.

 

45°

H1

H3 V2

 

 

 

H2

 

 

 

 

V1

90°

REQUIRED

VERTICAL

RISE IN

INCHES (VT)

HORIZONTAL VENT RUN PLUS OFFSETS IN FEET (HT)

V1

= 4 ft

V2

= 1.5 ft

VT

= V1 + V2 = 4 ft + 1.5 ft = 5.5 ft

H1

= 2 ft

H2

= 1 ft

H3

= 1 ft

H4

= 1.5 ft

HR

= H1 + H2 + H3 + H4 = 2 + 1 + 1 + 1. 5 = 5.5 ft

HO

= .03(one 45º elbow + three 90º elbow -135º)

 

=.03(315-135)=5.4ft

HT

= HR + HO = 5.5 +5.4 = 10.9 ft

HT + VT = 10.9 + 5.5 = 16.4 ft

Formula 1: HT < 4.2 VT

4.2VT = 4.2 x 5.5 = 23.1 ft

10.9< 16.8

Formula 2: HT + VT < 24.75 feet

16.4 < 24.75

The shaded area within the lines represents acceptable values for HT and VT .

For vent configurations requiring more than one 45º and 90° elbow the following formulas apply:

Formula 1: HT < 4.2 VT

Formula 2: HT + VT < 24.75 feet

Since both formulas are met, this vent configuration is ac- ceptable.

W415-0381 / C / 05.13.04