separate line must be branched o to the side burner unit and enter the side burner opening at the specied
locaon. If the enclosure is to house a propane cylinder, the tank poron of the enclosure must be venlated
according to local codes, and must not have communicaon with the cavity used to enclose the gas grill. A
propane cylinder can not be stored below the gas grill.
BUILT IN CYLINDER ENCLOSURES: Built in cylinder enclosures which completely enclose the cylinder must
have both of the following:
1. At least one unobstructed venlaon opening on the exposed exterior side of the enclosure located within
5 in (127 mm) of the top of the enclosure. The opening must have a total free area of more than 20 in2 (130
cm2)
for a 20 lb (9.1 kg) cylinder and 30 in2 (195 cm2) for a 30 lb (13.6 kg) cylinder.
2. At least one venlaon opening on the exposed, exterior side of the enclosure located 1 in (25.4 mm) or
less from the oor level. The opening must have a total free area of more than 10 in2 (65 cm2) for a 20 lb
(9.1 kg) cylinder and 15 in2 (100 cm2) for a 30 lb (13.6 kg) cylinder. The upper edge must be no more than 5
in (127 mm) above the oor level.
Every opening must be large enough to permit the entrance of a 1/8 in (3.2 mm) rod.
WARNING!
The cylinder valve(s) must be readily accessible for hand operaon. A door on the enclosure to gain
access to the cylinder valves is acceptable, provided it is non-locking and can be opened without the
use of tools.
The enclosure for the LP-gas cylinder must isolate the cylinder from the burner compartment to provide
shielding from radiaon, a ame barrier, and protecon from foreign material, such as hot drippings.
The enclosure cannot be located directly below the grill.
There must be a minimum clearance of 2 in (51 mm) between the oor of the LP-gas cylinder enclosure
and the ground.
The enclosure must be designed so that the LP-gas cylinder can be connected, disconnected and the
connecons inspected and tested outside the cylinder enclosure. Any connecons that can be disturbed
when installing the cylinder in the enclosure must be accessible for tesng inside the enclosure.
CYLINDER SIZE OPENING A AREA OPENING B AREA
20 lb (9.1 kg) 20 in2 (130 cm2) 10 in2 (65 cm2)
30 lb (13.6 kg) 30 in2 (195 cm2) 15 in2 (100 cm2)
5” (127 mm)
MAXIMUM
1” (25.4 mm)
MAXIMUM
OPENING
A
OPENING
B2” (51 mm)
MINIMUM
PARTITION TO ISOLATE
CYLINDER FROM GRILL
NON LOCKING DOOR
34” (864 mm)
RECOMMENDED
5” (127 mm)
MAXIMUM