© National Instruments Corporation 27 cFP-2200/2210/2220
Using the Reset Button
Pressing the Reset button resets the processor in the same manner as
cycling power.
Understanding LED Indications
Figure 30. LEDs

STATUS LED

The STATUS LED is off during normal operation. The cFP-22xx indicates
specific error conditions by flashing the STATUS LED a certain number of
times as shown in Table 3.
Table 3. Status LED Indications
Number of Flashes Indication
1The controller is unconfigured. Refer to the Measurement & Automation
Explorer Help for information about configuring the controller in MAX.
2The controller has detected an error in its software. This can occur
when an attempt to upgrade the software is interrupted. Refer to the
Measurement & Automation Explorer Help for information about
reinstalling software on the controller.
3The controller is in safe mode. Refer to the Configuring DIP Switches
section for information about the Safe Mode DIP switch.
4The software has crashed twice without rebooting or cycling power
between crashes. This usually occurs when the controller runs out of
memory. Review your RT VI and check the memory usage. Modify
the VI as necessary to solve the memory usage issue.
Solid The controller has detected an unrecoverable error. Please contact
National Instruments.