© National Instruments Corp. 5 FP-PG-522 and cFP-PG-522
Table1 lists the terminal assignments for the signals of each
channel. Terminal assignments are also listed on the side panel
ofthe cFP-PG-522 and under the slide-in card on the front of the
FP-PG-522.
Pulse Output Circuit
The [c]FP-PG-522 output channels are optically isolated from the
rest of the FieldPoint bank. In the ON state, a transistor is turned
on between the output (VOUT) and common (C and COM). In the
OFF state, this transistor is turned off, allowing only a small
leakage current to flow.
Ensure that the load on any channel does not draw more than 2A.
In addition, the sum of the squares of the channel currents must
notexceed 16 A2. For example, five channels operating at 1.2 A
yields 7.2A2:
(1.2 A)2 × 5 = 7.2 A2
Caution For a cFP-PG-522 operating in the 60–70 °C
temperature range, the sum of the squares of the channel
currents must not exceed 8 A2.
Table 1. Terminal Assignments
Channel
Terminal Numbers
VOUT1VSUP2COM
0 2 1,17 18
1 4 3,19 20
2 6 5,21 22
3 8 7,23 24
410 9,25 26
512 11,27 28
614 13,29 30
716 15,31 32
1 Install a 2 A maximum, fast-acting fuse on each VOUT terminal.
2 Install a 2 A maximum, fast-acting fuse on each VSUP terminal.