© National Instruments Corp. 11 FP-PG-522 and cFP-PG-522
following symbol stamped beside it: . Connect the
backplane PE ground terminal to the system safety ground
using 14AWG (1.6 mm) wire with a ring lug. Use the 5/16 in.
panhead screw shipped with the backplane to secure the ring
lug to the backplane PE ground terminal.
• As with any hazardous voltage wiring, make sure that all
wiring and connections meet applicable electrical codes and
commonsense practices. Mount terminal bases and backplanes
in an area, position, or cabinet that prevents accidental or
unauthorized access to wiring that carries hazardous voltages.
• Operate the [c]FP-PG-522 only at or below Pollution
Degree2. Pollution Degree 2 means that only nonconductive
pollution occurs in most cases. Occasionally, however, a
temporary conductivity caused by condensation must be
expected.
• Refer to the FieldPoint product label for regulatory
certification under hazardous location standards. If the
FieldPoint product is not certified for operation in hazardous
locations, do not operate it in an explosive atmosphere or
where there may be flammable gases or fumes.
SpecificationsThe following specifications are typical for a range of –40to 70°C
unless otherwise noted.
Output
Number of channels.......................... 8
Output type....................................... 5–30 VDC, sinking
Supply voltage.................................. 5–30 VDC, user-provided
Maximum output current
Per channel................................. 2 A per channel
Across all channels..................... 16 A2 (8 A2 for cFP-PG-522
operating at 60–70 °C)
Output impedance............................. 0.12 Ω
Pulse-width accuracy........................ ±5 µs, any pulse settings
Pulse-frequency accuracy.................0.007%, any pulse settings