FP-AI-110 and cFP-AI-110 16 ni.com
Physical CharacteristicsIndicators....................... ...................Green POWER and
READY indicators
Weight
FP-AI-110...................................140 g (4.8 oz)
cFP-AI-110.................................110 g (3.7 oz)
Power RequirementsPower from network module............350 mW
Safety Isolation VoltageChannel-to-ground isolation
Continuous.......... ....................... 250 Vrms, Measurement
CategoryII
Dielectric withstand....................2,300 Vrms (test duration
is5 s)
Channel-to-channel isolation............No isolation between
channels
EnvironmentalFieldPoint modules are intended for indoor use only. For outdoor
use, they must be mounted inside a sealed enclosure.
Operating temperature...................... –40 to 70 °C
Storage temperature.......................... –55 to 85 °C
Humidity........................................... 10 to 90% RH,
noncondensing
Maximum altitude.............................2,000 m; at higher altitudes
the isolation voltage ratings
must be lowered.
Pollution Degree............................... 2
Shock and VibrationThese specifications apply only to the cFP-AI-110.
NIrecommends Compact FieldPoint if your application
issubject to shock and vibration.
Operating vibration, random
(IEC 60068-2-64)..............................10–500 Hz, 5 grms
Operating vibration, sinusoidal
(IEC 60068-2-6)................................10–500 Hz, 5 g