FP-AI-110 and cFP-AI-110 8 ni.com
OverrangingThe [c]FP-AI-110 has an overranging feature that measures a little
beyond the nominal values of each range. For example, the actual
measurement limit of the ±10V range is ±10.4 V. The overranging
feature enables the [c]FP-AI-110 to compensate for field devices
with span errors of up to +4% of full scale. Also, with the
overranging feature, a noisy signal near full scale does not create
rectification errors.
Filter SettingsThree filter settings are available for each channel. The filters on
the [c]FP-AI-110 input channels are comb filters that provide
notches of rejection at multiples, or harmonics, of a fundamental
frequency. You can select a fundamental frequency of 50, 60, or
500Hz. The [c]FP-AI-110 applies 95 dB of rejection at the
fundamental frequency and at least 60 dB of rejection at each of
theharmonics. In many cases, most of the noise components of
input signals are related to the local AC power line frequency, so
afilter setting of either 50 or 60 Hz is best.
The filter setting determines the rate at which the [c]FP-AI-110
samples the inputs. The [c]FP-AI-110 resamples all of the channels
at the same rate. If you set all of the channels to the 50 or 60 Hz
filter, the [c]FP-AI-110 samples each channel every 1.470s or
every 1.230s, respectively. If you set all of the channels to 500 Hz
filters, the module samples each channel every 0.173s. When you
select different filter settings for different channels, use the
following formula to determine the sampling rate.
(number of channels with 50 Hz filter) ×184 ms +
(number of channels with 60 Hz filter) ×154 ms +
(number of channels with 500 Hz filter) × 21.6 ms =
Update Rate
If you are not using some of the [c]FP-AI-110 channels, set them
tothe 500 Hz filter setting to improve the response time of the
module. For example, if one channel is set for a 60Hz filter, and
the other seven channels are set to 500Hz, the module samples
each channel every 0.3s (four times faster than the case in which
all eight channels are set to the 60Hz setting).
The sampling rate does not affect the rate at which the network
module reads the data. The [c]FP-AI-110 always has data available
for the network module to read; the sampling rate is the rate at
which this data is updated. Set up your application so that the