FP-RTD-124 and cFP-RTD-124 12 ni.com
Physical Characteristics
Indicators....................... ...................Green POWER and
READY indicators
Weight
FP-RTD-124...............................140 g (4.8 oz)
cFP-RTD-124............................. 110 g (3.7 oz)
Power Requirements
Power from network module............350 mW
Isolation Voltage
Channel-to-channel isolation............No isolation between
channels
Transient overvoltage........................2,300 Vrms
Environmental
FieldPoint modules are intended for indoor use only. For outdoor
use, FieldPoint modules must be mounted inside a sealed
enclosure.
Operating temperature...................... 40 to 70 °C
Storage temperature.......................... 55 to 100 °C
Humidity........................................... 10 to 90% RH,
noncondensing
Maximum altitude.............................2,000 m
Pollution Degree............................... 2
Shock and Vibration
Operating shock (IEC 68-2-27)
cFP-RTD-124..............................50 g, 3 ms half sine, 3 shocks;
30 g, 11 ms half sine,
3shocks
Operating vibration, random (IEC 60068-2-34)
FP-RTD-124............................... 10500 Hz, 2.2 grms
cFP-RTD-124............................. 10500 Hz, 5 grms
Operating vibration, sinusoidal (IEC 60068-2-6)
[c]FP-RTD-124...........................10500 Hz, 5 g