FP-RTD-124 and cFP-RTD-124 4 ni.com
Wiring the [c]FP-RTD-124The FP-TB-x terminal bases have connections for each of the eight
input channels on the FP-RTD-124. The cFP-CB-x connector
blocks provide the same connections for the cFP-RTD-124.
Table1 lists the terminal assignments for the signals associated
with each channel.
If you are using shielded wiring, you can reduce input signal noise
by connecting one end of the shield to the COM terminal. Do not
connect the shield to any of the wires at the signal end.
Taking RTD Measurements with the [c]FP-RTD-124The [c]FP-RTD-124 has eight input channels. All eight channels
share a common ground that is isolated from other modules in the
FieldPoint system. Each channel pulses a 2mA excitation current
out of the EXCITE+ terminal. The excitation current returns
through the COM terminal. The SENSE+ and SENSE– terminals
measure resistance and compensate for lead resistance errors. Each
channel is filtered, then sampled by a 16-bit analog-to-digital
converter.
Table 1. Terminal Assignments
Channel
Terminal Numbers
SENSE+ SENSE– EXCITE+ COM
0 1 2 17 18
1 3 4 19 20
2 5 6 21 22
3 7 8 23 24
4 9 10 25 26
511 12 27 28
613 14 29 30
715 16 31 32