NI 9235/9236 4ni.com
Caution Substitution of components may impair
suitability for Class I, Division 2.
Caution For Zone 2 applications, install the system
in an enclosure rated to at least IP54 as defined by
IEC 60529 and EN 60529.
Caution For Zone 2 applications, connected signals must
be within the following limit:
Capacitance.......................... 0.2 μF max
Special Conditions for Hazardous Locations Use in Europe
This equipment has been evaluated as Ex nA IIC T4 equipment
under DEMKO Certificate No. 07 ATEX 0626664X. Each module
is marked II 3G and is suitable for use in Zone 2 hazardous
locations. If you are using the NI 9235/9236 in Gas Group IIC
hazardous locations or in ambient temperatures of
–40°CTa 70 °C, you must use the device in an NI chassis
that has been evaluated as EExnC IIC T4, Ex nA IIC T4, or
ExnL IIC T4 equipment.