Chapter 2 Installation and Configuration
© National Instruments Corporation 2-11 NI PXI-1056 User Manual
Temperature Measurement CommandsNote Units are in degrees Celsius.
Fan Speed Measurement CommandsCommand Response Description
TA TA:<CR><LF>
T1: +XX<CR><LF>
T2: +XX<CR><LF>
T3: +XX<CR><LF>
Transmit all temperatures
T1 T1: +XX<CR><LF> Transmit temperature sensor #1 value
T2 T2: +XX<CR><LF> Transmit temperature sensor #2 value
T3 T3: +XX<CR><LF> Transmit temperature sensor #3 value
ST ST:T1: x <CR><LF> Temperature sensor #1, x = OK or FAIL
ST:T2: x <CR><LF> Temperature sensor #2, x = OK or FAIL
ST:T3: x <CR><LF> Temperature sensor #3, x = OK or FAIL
Command Response Description
FA FA:<CR><LF>
F1: XXXX RPM<CR><LF>
F2: XXXX RPM<CR><LF>
F3: XXXX RPM<CR><LF>
F4: XXXX RPM<CR><LF>
Transmit all fan speeds
F1 F1: XXXX RPM<CR><LF> Transmit fan speed #1 value
F2 F2: XXXX RPM<CR><LF> Transmit fan speed #2 value
F3 F3: XXXX RPM<CR><LF> Transmit fan speed #3 value
F4 F4: XXXX RPM<CR><LF> Transmit fan speed #4 value