National Instruments NI UES-3880 manual Grounding the Switch, Wiring the Alarm Contact

Models: NI UES-3880

1 14
Download 14 pages 39.15 Kb
Page 7
Image 7
Grounding the Switch

You should also pay attention to the following items:

yUse separate paths to route wiring for power and devices. If power wiring and device wiring paths must cross, make sure the wires are perpendicular at the intersection point.

yNOTE: Do not run signal or communications wiring and power wiring in the same wire conduit. To avoid interference, wires with different signal characteristics should be routed separately.

yYou can use the type of signal transmitted through a wire to determine which wires should be kept separate. The rule of thumb is that wiring that shares similar electrical characteristics can be bundled together.

yKeep input wiring and output wiring separated.

yIt is strongly advised that you label wiring to all devices in the system when necessary.

Grounding the Switch

Grounding and wire routing help limit the effects of noise due to electromagnetic interference (EMI). Run the ground connection from the ground screw to the grounding surface prior to connecting devices.

ATTENTION

This product is intended to be mounted to a well-grounded mounting surface, such as a metal panel.

Wiring the Alarm Contact

The Alarm Contact consists of the two middle contacts of the terminal block on the NI UES-3880’s top panel. You may refer to the next section for detailed instructions on how to connect the wires to the terminal block connector, and how to attach the terminal block connector to the terminal block receptor. In this section, we explain the meaning of the two contacts used to connect the Alarm Contact.

FAULT

Top View

FAULT

Front View

FAULT: The two middle contacts of the

6-contact terminal block connector are used to detect both power faults and port faults. The two wires attached to the Fault contacts form an open circuit when:

1.The NI UES-3880 has lost power from one of the DC power inputs.

OR

2.One of the ports for which the corresponding PORT ALARM DIP Switch is set to ON is not properly connected.

If neither of these two conditions is satisfied, the Fault circuit will be closed.

Wiring the Redundant Power Inputs

The top two contacts and the bottom two contacts of the 6-contact terminal block connector on the NI UES-3880’s top panel are used for the NI UES-3880’s two DC inputs. Top and front views of one of the terminal block connectors are shown here.

— 6 —

Page 7
Image 7
National Instruments NI UES-3880 manual Grounding the Switch, Wiring the Alarm Contact, Wiring the Redundant Power Inputs