Note Software scaling of measurements is not supported on the Macintosh operating system. Refer to the SCC-AO10 Connector Pin Assignments section.

You can download NI documents from ni.com/manuals. To download the latest version of NI-DAQmx, click Download Software at ni.com.

Device Specific Information

Note For general SCC module installation and signal connection information, and information about the SC-2345/2350 carrier, refer to the SCC Quick Start Guide, available for download at ni.com/manuals.

Installing the SCC-AO10

Caution Refer to the Read Me First: Safety and Radio-Frequency Interference document before removing equipment covers or connecting/disconnecting any signal wires.

Plug the SCC-AO10 into either SC-2345/2350 analog output socket

J(X+17), where X is 0 or 1. The SC-2345/2350 routes the voltage output of

E/M Series DAQ device analog output channel AO (X) to the SCC-AO10.

Connecting the SCC-AO10 to a Load

Caution Refer to the Read Me First: Safety and Radio-Frequency Interference document before removing equipment covers or connecting/disconnecting any signal wires.

Note The signal names have changed. Refer to ni.com/info and enter rdtntg to confirm the signal names.

The SCC-AO10 has a three-pin screw-terminal connector that accepts 28 to 16 AWG wires.

The screw terminals are labeled by pin numbers 1 to 3. Pin 1 is the isolated ground. Pins 2 and 3 both connect to the isolated voltage output for flexibility in field wiring.

Caution Connecting an external voltage source to the output terminals of the SCC-AO10 may damage the module.

© National Instruments Corporation

3

SCC-AO10 Isolated Analog Output Module User Guide