Managed Layer 2 Switches GSM7224R and GSM7248R Hardware Installation Guide
Installation
Install the equipment in the following sequence, as presented in this chapter:
1.Select a location. See the following section, “Selecting a Location.”
2.Install the switch. See “Installing the Switch” on page
3.Check the installation. See “Checking the Installation” on page
4.Apply power and check the LEDs. See “Connecting to Power and Check the LEDs” on page
Selecting a Location
The switch can be mounted in a standard
Table 2-1. Site Requirements for Switch Location
Requirements
Mounting | • Desktop Installations. Provide a flat table or shelf surface. | |
| • | |
| equipment rack that is grounded and physically secure, and the | |
| supplied with your switch. | |
|
| |
Access | Put the switch in a position that lets you access the front panel | |
front panel LEDs, and access the rear panel power connector. | ||
| ||
|
| |
| Provide a power source within 6 feet (1.8 meters) of the installation location. Power | |
Power source | specifications for the switch are shown in Appendix A, “Default Settings and | |
Technical Specifications.” Be sure that the AC outlet is not controlled by a wall switch, | ||
| ||
| which can accidentally turn off power to the outlet and the switch. | |
|
| |
Environment | Install the switch in a site free from strong electromagnetic field generators (such as | |
| motors), vibration, dust, and direct exposure to sunlight. | |
|
| |
Temperature | The ambient switch operating temperature range is 0º to 55ºC (32º and 131ºF). Keep | |
| the switch away from heat sources such as direct sunlight, | |
| vents, and heaters. | |
|
| |
Operating humidity | Install the switch in a dry area with a maximum relative humidity of 90%, | |
| noncondensing. | |
|
|
Hardware Installation |