New Buck Corporation 1127B manual Ventilation Air From Inside Building

Models: 1127B

1 43
Download 43 pages 22.24 Kb
Page 17
Image 17
VENTILATION AIR

VENTILATION AIR

VENTILATION AIR FROM INSIDE BUILDING

This fresh air would come from an adjoining unconfined space. When venting to an adjoining space, you must provide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see Options 1 and 2, Figure 8). You can also remove door into adjoining room (see Option 3, in Figure 8).

NOTE: Each opening shall have a minimum free area of 1 square inch per 1000 BTU’s per hour of the total input rating of all gas utilization equipment in the confined space, but not less than 100 square inches.

Figure 8

15

Page 17
Image 17
New Buck Corporation 1127B manual Ventilation Air From Inside Building