NEW BUCK CAST COLLAR
Part # MA6CHIMCNB
C. Vertical wall exit using (6" Single Wall Pipe minimum 24 ga. blued or black pipe and elbow pipe, and any listed 2100° UL 103 HT. TYPE Chimney and Listed 2100° UL HT T-Box assembly). With standard close clearance shield and pipe shield. Model 261 minimum clearance to combustibles.
CC
C
C

NOTE: All clearances are to combustibles with all low clearance shields and single wall pipe

with elbow, and minimum floor protector.NOTE: Floor protector must extend length of

horizontal flue pipe to wall. NOTE: Model 261 comes standard with low clearance shields.

Figure 7.
SINGLE WALL
CONNECTOR
ELBOW PIPE
IN
SIDE
WALL
CEILING Maintain 18"Minimum Clearance
WALL
PASS-THROUGH
CONNECTOR
CENTER LINE
OF ELBOW
MARK PLUMB
LINE ON WALL
LISTED 2100° UL 103 HT TYPE
CHIMNEY REEFER TO
MANUFACTURERS
INSTALLATION INSTRUCTION
LISTED 2100° UL 103 HT
TYPE CHIMNEY T-BOX
ASSEMBLY REEFER TO
MANUFACTURES
INSTALLATION
INSTRUCTION
Figure 8.
BACK
WALL
A
E
B
F
D
G
A
E
B D
F
BACK WALL
SIDE WALL
PROTECTOR
G

A B C D E F G H

MODEL 261 13” 7" 13" 12" 8" 3" 16" 10"
H
NOTE: