Nextar NP-610X Installation Instructions, Mounting Instructions, Location Considerations

Models: NP-610X

1 32
Download 32 pages 54.17 Kb
Page 8
Image 8

Chapter 2 Installation Instructions

2.1 Mounting Instructions

2.1.1 Location Considerations

Care should be taken when locating equipment behind the unit to ensure that AC power wiring, PLC output modules, contactors, starters and relays, and any other source of electrical interference are located away from the back of the unit.

Particular note should be taken to the position of variable speed drives and switching power supplies. Their input and load cables should be screened to a central star earth point.

2.1.2 Making a NEMA-4 Mounting

Panel Details

The unit can be mounted into panels with a depth of 1.72”(51 mm).

 

It is recommended that the unit be mounted on the front panel of a

 

steel enclosure, through an appropriate opening*. Allow a clearance

 

of 1”(25mm) around the sides of the unit for mounting hardware .

 

Allow clearance for cable connections to the back of the unit. Unit

 

depth may vary according to cable type used. Typically, plan a depth

 

to accommodate at least 1.72”(51mm) behind the panel.

NEMA-4

Put the unit through the panel cut out. Slide the clamps into the 6

Mounting

holes provided around the case. Tighten the clamping screws in an

 

even pattern until the unit is secured in the panel.

Caution!

Do not over tighten mounting clamps!

Note:

Specifications Note:

 

To seal to NEMA-4 specifications, all supplied mounting clamps

 

must be used and panel cannot flex more than 0.010”.

8

Page 8
Image 8
Nextar NP-610X Installation Instructions, Mounting Instructions, Location Considerations, Making a NEMA-4 Mounting