9. Technical specifications

Type mark:

Type

 

434

 

834

1534

2364

3264

4564

6564

Heating voltage

Volt

 

 

 

400 Volt, 50/60 Hz

 

 

 

Number of phases

~

 

3

 

3

3

3

3

3

3

Heating current

A

 

4.4

 

8.8

16.5

25.2

35.1

49.4

71.3

External fuses p. phase

A

 

10

 

16

25

40

50

80

100

Type mark:

Type

422

432

822

832

1532

2362

3262

 

 

Heating voltage

Volt

 

 

 

230 Volt, 50/60 Hz

 

 

 

Number of phases

~

1

3

1

3

3

3

3

 

 

Heating current

A

13.2

7.6

26.4

15.3

28.6

43.9

61.0

 

 

External fuses p. phase

A

20

16

40

25

40

63

100

 

 

Steam output

kg/h

4

4

8

8

15

23

32

45

65

Minimum capacity

kg/h steam

0.8

0.8

1.6

1.6

3

4.6

6.4

9

13

Nominal power

kW

3.0

3.0

6.1

6.1

11.4

17.5

24.3

34.2

49.4

Design data:

 

 

 

 

 

 

 

 

 

 

Dimensions

width mm

354

354

354

354

490

490

490

490

490

 

height mm

562

562

562

562

672

672

672

672

672

 

depth mm

210

210

210

210

340

340

340

340

340

Steam outlet diameter

mm

1x22

1x22

1x22

1x22

1x35

1x35

1x35

2x35

2x35

Weight (empty)

kg

11.5

11.5

12

12

20

21

22.5

24

24

Operating weight

kg

15

15

18.5

18.5

35

36

47.5

49

49

Accessories:

 

 

 

 

 

 

 

 

 

 

Humidity controller

qty

1

1

1

1

1

1

1

1

1

Control electronics:

 

 

 

 

 

 

 

 

 

 

Supply voltage

Volt

 

 

220–240

Volt, 50/60 Hz,

1~

 

 

Proportional adaptor

qty

1

1

1

1

1

1

1

1

1

Steam distributors for

dct use:

 

 

 

 

 

 

 

 

 

Steam nozzle

qty

1

1

 

 

 

 

 

 

 

22-xxx mm

qtv

1

1

1

1

 

 

 

 

 

35-300 mm

qty

 

 

 

 

1

 

 

 

 

35-450 mm

qty

 

 

 

 

1

1

 

2

 

35-600, 35-900 mm

qty

 

 

 

 

1

1

1

2

2

35-1200, 35-1500 mm

 

 

 

 

 

 

 

 

 

 

Steam hose:

 

 

 

 

 

 

 

 

 

 

Ø 22/29 mm

qty x m

1

1

1

1

 

 

 

 

 

Ø 35/43 mm

qty x m

 

 

 

 

1

1

1

2

2

Condensate hose:

 

 

 

 

 

 

 

 

 

 

Ø 6/10 mm

qty x m

1

1

1

1

1

1

1

2

2

Steam blowers for direct

room humidification

 

 

 

 

 

 

 

 

Split mounted

qty

1

1

1

1

1

1

1

1

1

Other heating voltages on request.

Manufacturer:

Walter Meier (Climate international) ltd.

talstr. 35-37, P.O. Box, CH-8808 Pfäffikon (switzerland) Phone +41 55 416 61 11, Fax +41 55 416 62 62 nordmann@waltermeier.com / www.nordmann-engineering.com

Page 16
Image 16
Nordmende 2401935EN0801 manual Technical specifications, 4564