Steam-distribution pipe fitted on suction side:

Pressure- compensation

Tight-fitting hose rubber bung

Stench trap

Type: Sperrfix 3

Fig. 3.21

Because of the under-pressure in the appliance or the duct part, condensate may be kept back in the steam-distribution pipe. If there is an outlet in the empty part of the humidifier, the condensate can be bled off in the immediate vicinity.

An alternative method of bleeding off the condensate can be seen in the diagram.

3.5 Fitting the blowers

For the humidifier to work best, correct steam distribution is essential. For this reason, the minimum distances must be observed when installing the equipment.

Please note that only wall installation is possible with the econoVap.

Minimum distances for steam blowers 4-23 kg/h

A

B

Fig. 3.22

Type

A

B

 

min.

min.

4 kg

600 mm

3 m

 

 

 

8 kg

900 mm

5 m

 

 

 

15 kg

1000 mm

7 m

 

 

 

23 kg

1000 mm

10 m

 

 

 

Minimum distances for steam blowers 32-65 kg/h

Typ 32: min. 1500 mm

Typ 45: min. 2000 mm

min.

15 m

Fig. 3.22

450 mm

450