Nordmende 2401935EN0801 manual Water connections, Water quality, Laying the condensate hose

Models: 2401935EN0801

1 16
Download 16 pages 55.27 Kb
Page 10
Image 10
3.7 Laying the condensate hose

3.7 Laying the condensate hose

Condensate

fed back to

the unit

Condensate

drained off

separately

Fig. 3.29

It is advisable to lay the condensate hose as near to the ver- tical as possible and to feed the condensate either directly into an open funnel or below the siphon.

If the steam-distribution pipe is fitted above the humidifier, the condensate can be fed back to the unit by placing the end of the hose in the filling cup. In this case a small siphon should be for- med with the condensate hose.

If the condensate is drained off directly, it is advisable to feed back the condensate hose separately. The end of the condensate hose should be in the open air, if the end of the hose is submer- ged in water, the condensate is prevented from draining away freely.

4 Water connections

4.1 Water quality

NORDMANN humidifiers use ordinary tap water for the production of pure steam. The electrical conductivity should be between 125 and max. 1250 microSiemens per cm.

The hardness of water is measured in accordance with the international unit millimol calcium and magnesium ions per litre (mmol/l), previously in degrees of German hardness (DH).

Soft water:

up to 1.3 mmol/l up to 7 ° DH

Fairly hard water:

1.3 bis 2.5 mmol/l 7-14 ° DH

Hard water:

2.5 bis 3.8 mmol/l 14-21 ° DH

Very hard water:

over 3.8 mmol/l over 21 ° DH

Other international units:

1° DH = 1.79° French hardness

 

1° DH = 1.25° English hardness

 

1° DH = 1.05° US hardness

 

1° DH = 10 mg/l CaO

 

1° DH = 17.9 mg/l CaCO3 (ppm)

NORDMANN's electrode steam humidifiers function with water ranging from soft to very hard, without the need for prior treatment.

However, for fairly hard water and above, we recommend the use of the SC System (NORDMANN’s patented self cleaning system), which greatly reduces the amount of maintenance required for the cylinder. The SC System is available as option built-in ex works or as a retrofit option.