Control Module Status Indicators - M1M Series

Control Status

The Red LED labeled “STATUS” is provided to indicate system faults.

Steady ON:

Control OK

Steady OFF:

No power

Rapid flash:

False flame or internal control fault

One flash:

Limit switch is open

Two flashes:

Pressure switch is open

Three flashes:

Pressure switch is stuck closed

Four flashes:

Lockout due to failed ignition

Five flashes:

L1 neutral reversed or L1 voltage

 

not present on L1

Flame Status

A Yellow LED labeled “Flame” is provided to indicate flame status. When flame is sensed, the flame LED is lit. If flame sense is weak, yellow LED will flash.

Control Module Status Indicator - M1B

a. One flash-the control is in lock-out because the inducer centrifu gal switch is or was stuck closed.

b. Two flashes-the control is in lockout because the signal was not received by the control that the inducer centrifugal switch had closed within the time.

c. Three flashes-the control is in lockout because a failed ignition attempt, a gas valve error, or a false flame sensed during the warm up period. If false flame has been sensed, the control will return to normal operation, and repeat ignition sequence when the false flame is not present.

d. Four flashes-the control is in lockout due to a failure within the control board.

Control Module Status Indicator - M1S* Series

The indicator light on the oil primary control provides lockout, recycle, and cad cell indications as follows:

1.Flashing 1/2 second on, 1/2 second off - system is locked out or in restricted mode.

2.Flashing 2 seconds on, 2 seconds off - control is in recycle mode.

3.Indicator light is on - cad cell is sensing flame.

4.Indicator light is off - cad cell is not sensing flame.

may be defective. Replace the gas valve if necessary.

e. Be sure the pilot shield is in place.

f.Check for gas leaks in the pilot line or the pilot assembly.

g.Check the flue assembly to make sure all connections are tight.

h.See the FURNACE START-UP procedure for lighting details.

Main Flame Is Not Burning Properly a. Check the manifold gas pressure.

b. Check for the correct main burner orifice. - See the nameplate SPECIFICATION.

c. Check the flue for any blockages or loose connections.

d.Check the combustion air passages for block- age.

High Gas Bills

a. Be sure the proper orifices are being used.

b.Be sure the return air system is clear and free of blockage.

c.Be sure the furnace filter is clean.

d.Be sure the home is insulated, that windows and doors fit tightly, and that there are no leaks in the heating duct system.

e.Check the room thermostat to be sure the setting is not higher than necessary. Low

28

Page 28
Image 28
Nordyne M1G, M1B, M1S owner manual Control Module Status Indicators M1M Series

M1M, M1S, M1B, M1G specifications

Nordyne, a renowned player in the HVAC industry, has introduced a range of high-efficiency gas furnaces, including the M1S, M1G, M1B, and M1M models. Each of these furnaces is designed to provide efficient heating solutions tailored to the needs of homeowners.

The M1S series is well-known for its reliability and performance. It features a single-stage heating process that delivers consistent warmth to any space. With its multi-speed blower, the M1S ensures quiet and comfortable airflow, adapting seamlessly to varying temperature demands. Its robust construction coupled with an energy-efficient design makes it an ideal choice for those looking for dependable heating without sky-high utility bills.

The M1G model steps it up with a two-stage heating system that offers enhanced comfort and efficiency. By operating at a lower speed during milder conditions, the M1G can effectively reduce energy consumption while still maintaining a cozy environment. It is equipped with a variable-speed blower that not only enhances efficiency but also minimizes noise, making it perfect for residential areas. The M1G is designed with advanced safety features, including an integrated control board that monitors furnace functions to ensure optimal performance.

For those seeking a budget-friendly option without compromising on quality, the M1B model provides a solid performance with its straightforward, reliable single-stage heating. While it may lack some of the advanced features found in higher-end models, the M1B is built for ease of use with straightforward controls and maintenance, making it a great option for families.

The M1M model integrates cutting-edge technology with a focus on maximum efficiency. Featuring a modulating gas valve, this model can adjust its output based on real-time heating requirements. This adaptability ensures that the furnace operates at peak efficiency, significantly lowering energy bills and improving overall comfort. The M1M also boasts advanced diagnostic capabilities that allow for easy troubleshooting, thus reducing maintenance time and costs.

In summary, Nordyne's M1 series furnaces—M1S, M1G, M1B, and M1M—offer a range of options to meet diverse heating needs. With technologies designed for efficiency, reliability, and comfort, Nordyne continues to solidify its reputation as a leader in the HVAC market, providing homeowners with effective heating solutions tailored to their lifestyles and budgets.