14

Table 2a. Q4SA Heating

Q4SA-060

OUTDOOR TEMPERATURE (° F)

 

 

0

 

 

10

 

 

 

20

 

 

30

 

 

 

40

 

 

50

 

 

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Suc.

Disch.

Disch.

Suc.

Disch.

Disch.

Suc.

Disch.

Disch.

Suc.

Disch.

Disch.

Suc.

Disch.

Disch.

Suc.

Disch.

Disch.

Suc.

Disch.

Disch.

 

Press.

Press.

Temp.

Press.

Press.

Temp.

Press.

Press.

Temp.

Press.

Press.

Temp.

Press.

Press.

Temp.

Press.

Press.

Temp.

Press.

Press.

Temp.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

122

126

19

139

127

 

26

156

127

33

172

128

 

41

179

135

51

199

148

61

220

161

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

129

124

20

145

125

 

27

160

125

34

176

126

 

42

186

132

52

206

143

62

227

155

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14

136

122

21

151

123

 

28

165

123

35

180

124

 

43

193

129

53

213

139

63

234

149

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

15

143

120

22

156

121

 

29

170

121

36

183

122

 

44

200

126

54

220

134

64

241

143

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

16

150

118

23

162

119

 

30

175

119

37

187

120

 

45

207

123

55

227

130

65

248

136

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

17

157

116

24

168

117

 

31

179

117

38

191

118

 

46

214

120

56

234

125

66

255

130

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18

164

114

25

174

115

 

32

184

115

39

194

116

 

47

221

118

57

241

121

67

262

124

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat Pump in Heating

Charging Charts

*Note: All pressures are listed in psig. and all temperatures in deg. F.

— Shaded Boxes indicate flooded conditions

— Rated Design Values. Suction Pressure will be lower than design value if indoor air flow, entering dry bulb, or entering wet bulb temperatures are lower than design.

Discharge temperatures greater than charted values indicates a refrigerant undercharge.

Page 14
Image 14
Nordyne Q4 Series installation instructions Charging Charts, Q4SA-060