Nordyne R-410A Module Wiring Troubleshooting, OUTDOOR THERMOSTAT if supplied

Models: R-410A

1 24
Download 24 pages 38.33 Kb
Page 13
Image 13
Table 2. Module Wiring Troubleshooting

Miswired Module Indication

Recommended Troubleshooting Action

Green LED is not on,

Determine if both R and C module terminals are

module does not power up

connected. Verify voltage is present at module’s R and

 

C terminals. Review 24VAC Power W iring (page 4) for

 

R and C wiring.

 

 

Green LED intermittent,

Determine if R and Y terminals are wired in reverse.

module powers up only

Verify module’s R and C terminals have a constant

when compressor runs

source. Review 24VAC Power W iring (page 4) for R

 

and C wiring.

 

 

TRIP LED is on but system

Verify Y terminal is connected to 24VAC at contactor

and compressor check OK

coil. Verify voltage at contactor coil falls below 0.5VAC

 

when off. Verify 24 VAC is present across Y and C when

 

thermostat demand signal is present. If not, R and C are

 

reverse wired.

 

 

TRIP LED and ALERT LED

Verify R and C terminals are supplied with 19-28VAC.

flashing together

 

 

 

ALERT Flash Code 3

Verify Y terminal is connected to 24VAC at contactor coil.

(Compressor Short Cycling)

Verify voltage at contactor coil falls below 0.5VAC when

displayed incorrectly

off.

 

 

ALERT Flash Code 5, 6 or 7

Check that compressor run and start wires are through

(Open Circuit, Open Start Circuit

module’s current sensing holes. Verify Y terminal is

or Open Run Circuit) displayed

connected to 24VAC at contactor coil. Verify voltage at

incorrectly

contactor coil falls below 0.5VAC when off.

ALERT Flash Code 6 (Open

Check that compressor run and start wires are routed

Start Circuit) displayed for Code 7

through the correct module sensing holes.

(Open Run Circuit) or vice versa

 

ALERT Flash Code 8

Determine if module’s Y terminal is connected. Verify Y

(Welded Contactor)

terminal is connected to 24VAC at contactor coil. Verify

displayed incorrectly

24VAC is present across Y and C when thermostat demand

 

signal is present. If not, R and C are reverse wired. V erify

 

voltage at contactor coil falls below 0.5VAC when off.

 

Review Thermostat Demand Wiring (page 4) for Y and C

 

wiring.

 

 

Table 2. Module Wiring Troubleshooting

for any unusual noises. If present, locate and determine the source of the noise and correct as necessary.

OUTDOOR THERMOSTAT (if supplied)

The outdoor thermostat prevents the electrical auxiliary heat (if used) from operating above a desired set point. Selection of the set point is determined from the building design heat load.

The thermostat is adjustable from 45°F to 0°F. The factory temperature setting is at 40°F.

Defrost Cycle Timer — The defrost cycle timer controls the time interval of the hot gas defrost after the defrost sensor closes. It is located in the lower left corner of the defrost control board. Three interval settings are available: 30 minutes, 60 minutes, and 90 minutes.Time setting selection is dependent on the climate where the unit is being installed.

Example 1. Dry climate of Southern Arizona. A 90 minute setting is recommended.

Example 2. Moist climate of Seattle, Washington. A 30 minute setting is recommended.

To set the cycle timer, place the timing pin on the defrost control board to the desired time interval post.

Note: All units are shipped from the factory with the default time setting of 30 minutes. Maximum heating performance can be achieved by setting the time to 90 minutes.

Defrost Test Procedure

1.Terminals“R”-”C”must have 18-30v present between them in order for time delay and defrost sequences to be initiated.

13

Page 13
Image 13
Nordyne R-410A Module Wiring Troubleshooting, OUTDOOR THERMOSTAT if supplied, Defrost Test Procedure