Miswired Module Indication | Recommended Troubleshooting Action |
Green LED is not on, | Determine if both R and C module terminals are |
module does not power up | connected. Verify voltage is present at module’s R and |
| C terminals. Review 24VAC Power W iring (page 4) for |
| R and C wiring. |
|
|
Green LED intermittent, | Determine if R and Y terminals are wired in reverse. |
module powers up only | Verify module’s R and C terminals have a constant |
when compressor runs | source. Review 24VAC Power W iring (page 4) for R |
| and C wiring. |
|
|
TRIP LED is on but system | Verify Y terminal is connected to 24VAC at contactor |
and compressor check OK | coil. Verify voltage at contactor coil falls below 0.5VAC |
| when off. Verify 24 VAC is present across Y and C when |
| thermostat demand signal is present. If not, R and C are |
| reverse wired. |
|
|
TRIP LED and ALERT LED | Verify R and C terminals are supplied with |
flashing together |
|
|
|
ALERT Flash Code 3 | Verify Y terminal is connected to 24VAC at contactor coil. |
(Compressor Short Cycling) | Verify voltage at contactor coil falls below 0.5VAC when |
displayed incorrectly | off. |
|
|
ALERT Flash Code 5, 6 or 7 | Check that compressor run and start wires are through |
(Open Circuit, Open Start Circuit | module’s current sensing holes. Verify Y terminal is |
or Open Run Circuit) displayed | connected to 24VAC at contactor coil. Verify voltage at |
incorrectly | contactor coil falls below 0.5VAC when off. |
ALERT Flash Code 6 (Open | Check that compressor run and start wires are routed |
Start Circuit) displayed for Code 7 | through the correct module sensing holes. |
(Open Run Circuit) or vice versa |
|
ALERT Flash Code 8 | Determine if module’s Y terminal is connected. Verify Y |
(Welded Contactor) | terminal is connected to 24VAC at contactor coil. Verify |
displayed incorrectly | 24VAC is present across Y and C when thermostat demand |
| signal is present. If not, R and C are reverse wired. V erify |
| voltage at contactor coil falls below 0.5VAC when off. |
| Review Thermostat Demand Wiring (page 4) for Y and C |
| wiring. |
|
|
Table 2. Module Wiring Troubleshooting
for any unusual noises. If present, locate and determine the source of the noise and correct as necessary.
OUTDOOR THERMOSTAT (if supplied)
The outdoor thermostat prevents the electrical auxiliary heat (if used) from operating above a desired set point. Selection of the set point is determined from the building design heat load.
The thermostat is adjustable from 45°F to 0°F. The factory temperature setting is at 40°F.
Defrost Cycle Timer — The defrost cycle timer controls the time interval of the hot gas defrost after the defrost sensor closes. It is located in the lower left corner of the defrost control board. Three interval settings are available: 30 minutes, 60 minutes, and 90 minutes.Time setting selection is dependent on the climate where the unit is being installed.
Example 1. Dry climate of Southern Arizona. A 90 minute setting is recommended.
Example 2. Moist climate of Seattle, Washington. A 30 minute setting is recommended.
To set the cycle timer, place the timing pin on the defrost control board to the desired time interval post.
Note: All units are shipped from the factory with the default time setting of 30 minutes. Maximum heating performance can be achieved by setting the time to 90 minutes.
Defrost Test Procedure
1.
13