Functional Checkout:
CAUTION:
If equipped with a compressor crankcase heater, wait 24 hours prior to performing a function checkout to allow for heating of the compressor crankcase. Failure to comply may result in damage and could cause premature failure of the system.
Indoor Blower — Set the thermostat function switch to COOLING and the fan switch to ON. Verify that the indoor blower is operating and that airflow is not restricted. Set the fan switch back to AUTO.
Blower Time Delay Relay (Select Models): A time delay relay may be provided with the unit and must be installed in the indoor section.The relay will keep the indoor blower running an additional 40 seconds for increased cooling efficiency after the outdoor unit shuts off. The relay has four terminals and one mounting hole.
Connect terminal “1” to load side of blower relay. Connect terminal: “2” to terminal “R” of T’stat. Connect terminal “3” to common terminal at blower relay or transformer. Connect terminal “4” to terminal “G” on T’stat.
rises above 575 psig, then the switch will open and
Short Cycle Protection — With the system operating in COOLING mode, note the setpoint temperature setting of the thermostat, and gradually raise the setpoint temperature until the outdoor unit and indoor blower
Comfort AlertTM Diagnostics (Select Models)
—The Comfort AlertTM diagnostics module facilitates troubleshooting heat pump and air conditioning system failures. This Comfort AlertTM module is designed only for
NOTE: This module does not provide safety protection! The Comfort AlertTM module is a monitoring device and cannot control or shut down other devices.
LED Description (See Figure 2)
POWERLED(Green):indicatesvoltageispresent at the power connection of the module.
ALERT LED (Yellow): communicates an abnormal system condition through a unique flash code. The ALERT LED will flash a number of times consecutively, pause and then repeat the process. The number of consecutive flashes, defined as the Flash Code, correlates to a particular abnormal condition. Detailed descriptions of specific ALERT Flash Codes are shown in Table 1 of this manual.