!WARNING:

Do not operate your furnace if you find any of the following conditions. Such conditions may allow toxic fumes to escape into your home:

Obstructions or restrictions in the vent pipe and/or chimney.

Holes or cracks in the vent pipe.

Visible corrosion in the vent pipe.

Horizontal vent pipes that do not slope upward.

6. Operating Instructions

READ THE SAFETY INFORMATION ON THE FOLLOWING PAGE BEFORE OPERATING.

!WARNING:

Should overheating occur, or the gas supply fail to shut off, shut off the manual gas valve to the furnace before shutting off the electrical supply.

Ifanyoftheaboveconditionsarefound in the vent pipe, call a qualified service technician to install new vent pipe.

For 80+ upflow and downflow models only: Burner Maintenance (NOx), If the second or eighth character of the model number is an “N” the furnace has factory installed NOx reduction inserts. The inserts reduce the NOx emissions of the furnace. The NOx reduction inserts are located in the first pass of the top portion of the heat exchanger. When the burners are operating, the flame should extend through the center of the NOx reduction inserts. The flame color should be blue, however some light yellow streaks may occur on the outer portions of the flame.

Inspect the burners, mounting brackets, and all other parts in the vestibule for signs of deterioration. The burner vestibule should be vacuumed clean and inspected annually.

!CAUTION:

Do not strike any of the internal electrical components while vacuuming.

! ADVERTISSEMENT:

En cas de température excessive, ou s’il est impossible de couper l’alimentationengaz,fermerlerobinet manuel d’alimentation en gaz du générateur d’air chaud avant de couper l’alimentation électrique.

These furnaces are equipped with roll-out limit switch(s), a vent safety switch, and a pressure switch (See Figures 1, 2, 3 and 4). The pressure switch verifies that the flame is receiving combustion air. If the flame is not drawn into the heat exchanger tube, the roll out limit switch or flame sensor, will shut the furnace down.

The vent safety switch shuts the furnace down if the vent becomes blocked or restricted.

Furnace Fails To Operate — If the furnace does not operate, check the following:

1)Is the thermostat operating properly?

2)Are the blower door(s) in place?

3)Is the furnace disconnect closed?

4)Has the circuit breaker tripped (or fuse blown)?

5)Is the gas turned on?

6)Is the filter dirty or plugged?

10