maintenance a step further than RO and all the GS Series components are ready for RO or DI water use as a standard.
(10)Contact your local Nortec representative for a quotation of a water treatment system suited for your application.
2.PREVENTIVE MAINTENANCE
(1)The installation manuals of the GS Series of Gas Steam humidifier come with a complete Maintenance chart in order to guide internal personnel in cleaning and monitoring activities. Like any other appliance the
(2)While in operation, the unit will blowdown scaled water through a drain pump keeping control on the water concentration based on steam output. For longer intervals between cleaning, the unit may be completely drained down to reduce the mineral concentration and bring in new fresh water in the system.
(3)The FTBD (Full Tank Blow Down) can be activated through the software or dip switches based on:
(a)Time of day setting. When the 25 - 400 hours interval (adjustable ) is reached the unit will wait until the set time of day before activating the full tank blowdown.
(b)External trigger using 24Vac signal from the building management system to the input terminal of the humidifier.
(4)Following the full tank blowdown, the unit will refill and perform a float check. Whenever possible, use this feature to reduce mineral accumulation in the system and reduce the time required to clean the interior of the reservoir.
3.PRE-CLEANING SEQUENCE
(1)When cleaning of the reservoir is required, use the tank
(2)Full Size Frontal Opening: Every GS Series Gas Steam Humidifier comes complete with a full size frontal opening to allow bottom cleaning of the tank and heat exchanger. This opening allows quick and easy cleaning without removing the steam outlet of the unit.