I.Indoor Freeze Protection
(1)
(2)The remote fault indication will allow service personnel to be advised of the unit’s operational status and the normally open drain valve will ensure the unit is drained if a power outage.
(3)Drain and fill lines outside of the cabinet, must be protected from freezing with heat trace. Unit must be enclosed in a weather enclosure with heat source.
(4)A remote alarm must be installed in case the unit faults using remote fault indication and status indication.
J.Outdoor Freeze Protection (Standard with all GS Outdoor Enclosures)
(1)Outdoor units are configured with the Keep Warm feature enabled to maintain the tank water temperature between 140ºF (60ºC) and 160ºF (71ºC). Included is a factory installed normally open drain valve that will ensure the unit drains in the event of a power outage. Also a
(a)
(b)
(c)
(d)
K.ON-LINE
(1)Nortec OnLine is a remote interactive communication package that allows satellite contacts to monitor, maintain and control a humidification center from any location worldwide using standard internet connections. This advanced software shows graphic representations of the humidifier and its key parameters (up to 75 functions).
L.LINKS 2
(1)Nortec LINKS 2 is the combination of LINKS (building management system communication hardware) and OnLine (Internet communication hardware) allowing humidifiers to communicate to a building management system (BMS) as well as the Internet. Up to 8 humidifiers can be connected to 1 LINKS 2 controller (1 master and 7 slaves). The controller is factory installed and is located internally to the humidifier. Simply specify at the time of order the operating protocol needed. LINKS 2 comes standard with Internet capabilities however OnLine service needs to be specified at time of order.
(2)Operating Protocols:
a)