1.PRINCIPLE OF OPERATION

1.PRINCIPLE OF OPERATION

A.Combustion System

(1)The combustion system is based on a fully modulating forced draft combustion air blower, a negative pressure regulated gas valve, and a 100% premix burner. On a call for humidity, the combustion air blower starts and creates a negative pressure across an orifice located at the air inlet.

(2)The blower is energized to purge the system, then the hot surface igniter is activated. During this time the electronic ignition module does a diagnostic check of safety systems including the air-proving switch, which senses the negative pressure at the air inlet orifice. After the function of the safety systems has been verified, the gas valve will open and the gas/air mixture is ignited by the hot surface igniter.

(3)If a flame is sensed by the flame sensor, the gas valve remains open and combustion continues. If a flame is not sensed, the above sequence is repeated to a maximum of three times after which the ignition module will lock out. The gas valve maintains a constant ratio air to gas independent of blower speed or external conditions. This air and fuel is thoroughly mixed in the blower and then forced through the burner ports where ignition occurs.

(4)Hot products of combustion are forced through a baffle inside the heat exchanger and then vented outside. The heat exchanger has a large flat surface to minimize scale build-up and promote scale shedding to the bottom of the tank. This self- cleaning action helps to maintain the efficiency of the heat exchanger while the smooth surfaces allow for easy cleaning when necessary.

(5)The GS 100 has a single removable combustion chamber/heat exchanger. The combustion system is duplicated on larger units with multiple chambers inside a common tank.

Table 1. Technical Data

 

 

 

UNIT TYPE

 

 

 

SPECIFICATION

GS 100

GS 200

GS 300

GS 400

GS 500

 

GS 600

Rated Capacity: lbs/hr*

25-105

25-210

25-315

25-420

25-525

 

25-630

 

 

 

 

 

 

 

 

Rated Capacity: kg/hr*

11-48

11-95

11-143

11-191

11-238

 

11-286

 

 

 

 

 

 

 

 

Input BTU/hr max

140,000

280,000

420,000

560,000

700,000

 

840,000

 

 

 

 

 

 

 

 

Input kJ/hr max

41

82

124

165

206

 

247

 

 

 

 

 

 

 

 

Flue Emissions

Low CO (< 10 ppm) and Low (NOx <40 ppm)

 

 

 

 

 

 

 

 

 

GSTC/GSP Rated Amps

1.1

1.9

2.7

3.5

4.3

 

5.2

 

 

 

 

 

 

 

 

Voltage/Phase

 

 

208-240/1 Standard

 

 

 

 

 

 

 

 

 

 

 

GSTC Outdoor Rated Amps

3.2

4.0

6.9

7.7

10.6

 

11.5

 

 

 

 

 

 

 

 

Voltage/Phase

 

 

208-240/1 Standard

 

 

 

 

 

 

 

 

 

 

 

GSTC/GSP Rated Amps

2.1

3.7

5.3

6.8

8.4

 

10

 

 

 

 

 

 

 

 

Voltage/Phase

 

 

120/1 Standard

 

 

 

 

 

 

 

 

 

 

 

GSTC Outdoor Rated Amps

6.3

7.4

13.7

15.2

21.0

 

22.6

 

 

 

 

 

 

 

 

Voltage/Phase

 

 

120/1 Standard

 

 

 

 

 

 

 

 

 

 

 