Nortec Industries NHRS Series Technical Data, Voltage, Phase, Rated K.W, Max. Ext, Capacity

Models: NHRS Series

1 26
Download 26 pages 63.63 Kb
Page 14
Image 14
Technical Data

 

 

Table 1.

Technical Data

 

 

 

 

 

 

 

 

 

NHRS Model

VOLTAGE

PHASE

 

RATED

RATED K.W.

MAX. EXT.

/ Capacity

 

 

 

AMPS

 

CIRCUIT

(lbs/hr)

 

 

 

 

 

PROTECTION

010 [11.25]

208

1

 

18.39

3.83

25

010 [11.25]

230

1

 

15.94

3.83

20

010 [11.25]

460

1

 

7.97

3.83

15

010 [11.25]

575

1

 

6.38

3.83

15

 

 

 

 

 

 

 

015

208

1

 

24.52

5.10

35

015

230

1

 

21.25

5.10

30

015

460

1

 

10.63

5.10

15

015

575

1

 

8.50

5.10

15

 

 

 

 

 

 

 

020 [22.5]

208

1

 

36.78

7.65

50

020 [22.5]

230

1

 

31.88

7.65

40

020 [22.5]

460

1

 

15.94

7.65

20

020 [22.5]

575

1

 

12.75

7.65

20

 

 

 

 

 

 

 

030

208

1

 

49.04

10.20

70

030

230

1

 

42.50

10.20

60

030

460

1

 

21.25

10.20

30

030

575

1

 

17.00

10.20

20

 

 

 

 

 

 

 

030 [33.75]

208

3

 

31.89

11.48

40

030 [33.75]

230

3

 

27.64

11.48

35

030 [33.75]

460

3

 

13.82

11.48

20

030 [33.75]

575

3

 

11.05

11.48

15

 

 

 

 

 

 

 

045

208

3

 

42.52

15.30

60

045

230

3

 

36.85

15.30

50

045

460

3

 

18.42

15.30

25

045

575

3

 

14.74

15.30

20

 

 

 

 

 

 

 

065 [67.5]

208

3

 

6379

22.98

80

065 [67.5]

220-240

3

 

55.28

22.98

70

065 [67.5]

460

3

 

27.64

22.95

35

065 [67.5]

575

3

 

22.11

22.95

30

 

 

 

 

 

 

 

090

460

3

 

36.85

30.60

50

090

575

3

 

29.48

30.60

40

 

 

 

 

 

 

 

135

460

3

 

55.27

45.90

70

135

575

3

 

44.22

45.90

60

 

 

 

 

 

 

 

180

460

3

 

73.70

61.20

100

180

575

3

 

58.96

61.20

80

10-10

Page 5 2008-02-18
Page 14
Image 14
Nortec Industries NHRS Series Technical Data, Voltage, Phase, Rated K.W, Max. Ext, Capacity, Amps, 10-10, NHRS Model