Nortec Industries NHRS Series E.Blower Pack, F.Short Absorption Manifolds, G.On / Off Controls

Models: NHRS Series

1 26
Download 26 pages 63.63 Kb
Page 24
Image 24
E.BLOWER PACK

E.BLOWER PACK

(1)Wall mounted direct steam distribution system allows for direct space/room humidification when steam introduction into a ducted system is not feasible. The factory assembled remote mounted blower pack includes an integral steam distributor, 3 direct drive fans.

F.SHORT ABSORPTION MANIFOLDS

(1)This distribution system will allow a short absorption distance to be obtained. Refer to SAM-e Engineering Manual Form #XX-247.

G.ON / OFF CONTROLS

(1)252-0259 – Humidistat, on/off, control or high limit, wall mounted. Standard with internal integrated humidity sensor and digital display. Adjustment range 0-100% relative humidity with ±3% relative humidity control. Can be calibrated in the field.

(2)132-9203 - Air Proving Switch, on/off, duct mounted, pressure differential switch, adjustable set point from 0.07 IWC to 12.0 IWC, good for positive, negative or differential pressure applications, stops humidifier if duct air pressure is not sensed. Turns humidifier off if air handler fails.

(3)252-0273 - Humidistat, on/off, control or high limit, duct mounted. Standard with external duct mounted humidity control. Can be calibrated in the field.

G.SSR COOLING KIT

(1)253-0620 - This kit is used for applications where ambient temperature exceeds 95ºF (35ºC). Provides additional cooling for the Solid State Relays for exceptional conditions.

H.KEEP WARM OPTION

(1)150-4561 - This feature allows the water temperature in the tank to be maintained at 160ºF (70ºC) for quick response from the unit upon a call for humidity.

I.REMOTE FAULT INDICATION PACKAGE

(1)150-8069 - This option provides four relays to monitor the humidifier remotely. Relays are:

(i)Steam Production

(ii)Unit fault

(iii)Service / Maintenance

(iv)Unit on

All relays are BMS ready.

J.NORTEC LINKS 2 OPTION

(1)This option provides monitoring and controlling of the humidifier from a BMS (Building Management System) using the industries leading communication protocols. BACnet, LonWorks, Johnson N2 or Modbus. Simply specify what operating protocol you are using at time or order. OnLine capabilities are standard. The OnLine service must be ordered.

10-20

Page 7 2008-02-18

Page 24
Image 24
Nortec Industries NHRS Series E.Blower Pack, F.Short Absorption Manifolds, G.On / Off Controls, G.Ssr Cooling Kit, 10-20