 Installation

1.Mounting the PTO generator to a trailer. 2. Mounting the PTO generator to concrete. Installation

Choose a location where the generator will not be exposed to rain, snow or direct sunlight. Common places for mounting your PTO generator are to a trailer or a cement slab. Make sure it is as close to the load as possible. This will make using the generator more convenient and reduce voltage drop.

The installation site must be free from water, moisture, or dust. Foreign matters, such as dust, dirt, sand, lint, or abrasive materials can cause damage if allowed inside the generator. All electrical components should be protected from excessive moisture or the insulation system will deteriorate and result in shorting out of the generating system.

1.Mounting the PTO generator to a trailer.

Use four(4) 5/8” grade 5 bolts to secure the PTO generator to the trailer.

Important: When trailer mounting the generator, select a trailer that is wide enough to withstand the torque of start-up and loading torque. Wheels that are not spaced properly could cause the trailer to tip over. The constant vibration of the generator can cause metal fatigue of the trailer base if the steel used is not thick enough. A PTO trailer is available from Northern, Item# 165959. Call 1-800-556-7885 to order.

WARNING DANGER PTO trailer or generator

 

may tip over and cause serious injury or death. Never

 

stand near an operating PTO generator. Always bolt

Mounting holes (4)

PTO base to a secure foundation or mounting slab.

3.Connecting the PTO generator to a tractor.4. Grounding5. Standby UseManual backgroundManual background 2. Mounting the PTO generator to concrete.

Use four(4) 5/8” grade 5 anchor bolts when mounting the generator on a cement slab.

3.Connecting the PTO generator to a tractor.

After the generator is firmly mounted, attach the PTO driveline to the generator then the tractor. Use a synchronized PTO driveline rated at 14 HP minimum. A PTO driveline is available from Northern,

Item# 165936. Call 1-800-556-7885 to order. Important: The angle of the driveline shall not exceed

15o in either the horizontal or vertical plane.

Manual backgroundManual backgroundManual backgroundManual backgroundManual background WARNING Always properly guard rotating parts. Failure to guard the power transmission mechanisms may result in serious injury or death.

Max. 15°

Top View

Driveline

Max. 15°

Side View

4. Grounding

This unit must be grounded. Drive a 3/4” or 1” copper pipe or rod into the ground near the generator. It must penetrate moist earth. Connect an approved ground clamp to the pipe. Run an 8 gauge copper wire from the clamp to the generator ground screw. Do not connect to a water pipe or a ground used by a radio system.

Manual backgroundManual backgroundManual backgroundManual backgroundManual background WARNING Always ground the generator. Electrical shock can kill.

5. Standby Use

If your generator is to be used as a standby electric power source in case of utility failure, it must be installed by a registered and licensed electrician and in compliance with all applicable state and local electrical codes.

Manual backgroundManual backgroundManual backgroundManual backgroundManual background WARNING Never connect any generator to any existing electrical system without an isolating, UL approved transfer switch installed by a licensed electrician.