Page 18
Image 18
5. Grounding the generator

Installation / Initial Set-Up

5. Grounding the generator

Always ensure the generator is properly grounded to prevent electrical shock.

You must always ground the generator by the following method when using the generator as a portable electrical source:

1)Drive a ¾” or 1” copper pipe or rod into the ground close to the generator. The pipe/rod must penetrate moist earth – the depth required will be dictated by local soil conditions. Consult with an electrician.

2)Connect an approved ground clamp to the pipe.

3)Run a 10 gauge wire from the clamp to the generator grounding post located on the rear of the generator head.

4)Do not connect the generator grounding post to a water pipe or a ground used by a radio system.

10 Ga. wire

 

Copper

Grounding

Pipe/Rod

 

Post

Ground

 

If a licensed electrician installs the generator with a connection to your building’s electrical circuit for use as a back-up power system, grounding may alternatively be completed through the building’s grounding system. Ask your electrician. If the generator is not grounded through your building’s electrical system, follow the procedure above.

Manual backgroundManual background WARNING:

Operating the generator when it is not properly grounded can result in electrical shock.

18