…4 | ELECTRICAL INSTALLATION |
|
| |
4.4 | Cable | Glands | 4.4.2 Conduit | Adaptors |
and Conduit Fixings |
| (N. American – | 0.5in) – Fig. 4.4 |
4.4.1 | Cable | Glands |
(IEC – 20mm) – Fig. 4.3 |
| |
|
| |
| Fig. 4.3 Cable Gland |
|
| (Supplied as standard) |
|
Warning.
•Rigid conduit must NOT be fitted to the controller.
•Controller adaptors must incorporate a face seal.
•Torque settings for the hubs and outer nuts on the specified adaptors is 20ft. lbs minimum, 25ft. lbs. maximum.
Information.
•Suitable adaptors for controller (mandatory for FM installations):
APPLETON
Reusable ONLY with replacement ferrule
O.Z. GEDNEY
Alternative
Face Seal
Face |
|
Seal |
|
Seal | Hub |
| |
(Present |
|
in O.Z. | Ferrule |
Gedney | |
Fittings) |
|
Outer Nut
Fig. 4.4 Conduit Adaptors
8