Omega CN3440 manual CableGlands N. American - 0.5in - Fig, Electrical Installation…, Information

Models: CN3440

1 24
Download 24 pages 24.72 Kb
Page 11
Image 11
4 ELECTRICAL INSTALLATION…

4 ELECTRICAL INSTALLATION…

4.4.3 CableGlands (N. American – 0.5in) – Fig. 4.5

Warning.

Controller glands must be fitted with a face seal.

Torque settings (hubs only) – 20ft. lbs minimum, 25ft. lbs. maximum.

Outer nuts – hand tight plus a half turn only.

Information.

Suitable Cable Glands: (mandatory for FM installations):

O.Z. GEDNEY SR-50-375 or SR-504

APPLETON

CG 3150 or CG-3150S (and STG- 50 sealing ring).

THOMAS & BETTS 2521.

When fitting cable glands to the controller, start with an outer gland and also temporarily fit a gland at the opposite end, to aid location of the transmitter gland plate. Fit and tighten glands consecutively from initial gland.

Alternative

Face Seal

Face

 

Seal

 

 

Hub

Fittings

 

vary

Illustration

slightly

typical for

for

O.Z.Gedney

different

 

makes

 

Outer Nut

Fig. 4.5 Cable Glands

9

Page 11
Image 11
Omega CN3440 manual CableGlands N. American - 0.5in - Fig, Electrical Installation…, Information