CN8240 & CN8260 Series Communications & Options

Relay, N.O.

Alarm Output

Option -AL1, -AL2: Relay, N.O. Alarm Output

Supply voltage*

Supply voltage*

 

+

N.O.

2

12

 

 

 

 

C

3

13

 

OUTPUT 2

 

 

 

 

+

N.O.

4

14

Load

5 amp fuse

N.O.

5

15

 

ALARM 1

 

 

 

 

 

C

6

16

Load

5 amp fuse

N.O.

7

17

 

ALARM 2

 

 

 

 

 

C

8

18

 

120-250 V

L1

9 21

2219

 

50-60 Hz

L2

1

2

 

 

 

 

0

0

 

 

 

Option Description: NO (Normally open) relay contact is closed when either alarm is active. The relay life is greater than 100,000 operations at 5 operations per second switching full load.

*Connect load and supply voltage per the following table:

Load Type

5 A Voltage Limit

Resistive dc

30 Vdc

 

 

Inductive ac (L/R = 7 ms)

20 Vdc

 

 

Resistive ac

250 Vac

Inductive ac (pF = 0.4)

150 Vac

 

 

Motor, ac, 1/6 hp

250 Vac

Tungsten Lamp, 360 W

120 Vac

RS-232

Communications

Option -C2: RS-232 (one-to-one) Communications

 

RCV

XMT

SIG GND

 

RS

 

232

 

 

 

 

 

 

 

485

 

B(-)

A(+)

SIG GND

RS

 

 

RCV

XMT

SIG GND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

1

 

1

 

 

2

23

24 12

3

 

13

Option Description: Provides a one-to-one connection between the controller and an RS-232 port. Computers, PLCs, or dumb terminals may be used to set and access controller data.

1

Page 4
Image 4
Omega Engineering CN8260, CN8240 Option -AL1, -AL2 Relay, N.O. Alarm Output, Option -C2 RS-232 one-to-one Communications