Omega Engineering CN8240, CN8260 manual Option -C4 RS-485 one-to-many Communications

Models: CN8260 CN8240

1 31
Download 31 pages 28.68 Kb
Page 5
Image 5

CN8240 & CN8260 Series Communications & Options

RS-485

Communications

Option -C4: RS-485 (one-to-many) Communications

 

RCV

XMT

SIG GND

RS

232

 

B(-)

A(+)

SIG GND

 

485

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

1

 

1

 

 

2

23

24 12

3

 

13

4

 

14

JMP 1

Option Description: Provides one-to-many communications.

Terminate the controller furthest from the computer by either connecting a 120-ohm, 1/4-watt resistor between ter- minals 23 and 24 or using jumper 1 located on the underside of the communications board as shown above.

Transducer

Power Supply

Options -XP1, -XP2, -XP3, -XP4: Transducer Power Supply

3

 

13

 

 

 

4

 

14

 

 

 

5

 

15

 

 

 

6

 

16

 

 

 

7

 

17

 

 

 

8

 

18

 

 

 

9

21

19

MA

 

22

T/C

RTD

MV

1

 

2

V

0

 

0

+

+

 

 

 

 

NOTE: FOR 2 WIRE RTD

 

 

 

 

JUMPER 18 & 20

0 to1 volt out = 0 to100% RH

(6 to 30 Vdc input)

Option Description: The transducer power supply option provides power to remote transducers. The transducer outputs, in turn, provide a signal to the controller input which can be scaled in the appropriate engineering units.

Option -XP1: 15 Vdc

Option -XP2: 12 Vdc

Option -XP3: 10 Vdc

Option -XP4: 5 Vdc

All options will provide at least 20 mA. The transducer circuitry is thermally protected from short circuits.