Security Levels / Selecting and Accessing Data
Operator access to data modifications has three modes of security: View Only, Set Point Changes Allowed and Programming. Each mode is selected from the back of the unit with a DIP switch setting.
Programming Mode
This mode, #1 ON, allows you to change all eight programmable settings. It is used for initial
1
2
3
4
ON
Set Point Changes Allowed
This mode, #2 ON, allows you to change all four set points: the High & Low Alarms,
1
2
3
4
ON
View Only Mode
This mode, ALL OFF, prevents any changes from being made. However, all the information, except the transducer range and transducer offset, is available
by pressing SELECT.
1
2
3
4
ON
Output & Input Terminal Connections
(All terminal connections are plug in Phoenix type)
Output
Terminals
| Output Terminals |
| ||
12. | High Level N.C. | amp | ||
| 11. High Level Com | |||
| 10.0 | |||
10. | High Level N.O. | |||
|
|
| ||
| 9. Sump ON N.C. | amp | ||
| 8. Sump ON Com | |||
| 10.0 | |||
| 7. Sump ON N.O. | |||
|
|
|
| |
6. | Low Level N.C. | amp | ||
5. | Low Level Com | |||
10.0 | ||||
4. | Low Level N.O. | |||
|
|
| ||
| 3. Sump ON N.C. | amp | ||
| 2. Sump ON Com | |||
| 10.0 | |||
| 1. Sump ON N.O. |
120 VAC
Power Supply
Power Supply
3.120 VAC - Com.
2.Ground
1. 120 VAC - Hot
24 Volt DC
Power Supply
(Unregulated)
Power Supply
3.24 VDC - Neg
2.Ground
1.24 VDC - Pos (+)
Sensor Input
4.
3.
2.Ground
1.+ 24 VDC Output
NOTE: Terminal #1 provides power for loop powered sensors.