SIGNAL OUTPUT module MS

The signal conditioner provides two different analog output signals, both proportional to the signal input.

Output in Current: 4 to 20 mA, terminals 9 - 10

Output in Voltage: 0 to 10 Vdc, terminals 11 - 12

Do not use both outputs simultaneously. Only one selection can be made.

The side label shows which one is selected.

CHANGING THE SIGNAL OUTPUT

1

3

4

5

6

H i

 

 

 

 

/ ALIMENTACION

INPUT / ENTRADA

 

 

 

 

SUPPLY

OUTPUTS / SALIDAS

 

mA

Vdc

+

-

+

-

Lo

7

9

10

11

12

 

FIG.5

 

 

All signal conditioners are delivered as a standard version, with the analog output selected as 4 to 20 mA, unless specified otherwise. To select a 0 to 10 V output, remove jumpers E and F as shown in Figure 6. Other non-standard output voltage and current ranges may be obtained by adding and/or replacing resistors given in Tables 2 and 3.

NON STANDARD OUTPUT

NON STANDARD OUTPUT

VOLTAGES

TABLE 2

CURRENTS

 

TABLE 3

Output

 

Value in K

for :

 

in V.

R29

R30

R31

R32

 

 

 

 

 

±10

49.9

-----

200

----

0 to 1

-----

-----

11

100

0 to 5

-----

-----

100

100

1 to 5

-----

100

66.5

100

 

 

 

 

 

Output

Value in for :

 

in mA.

R18

R24

R25

 

 

 

 

0 to 5

-----

100

-----

0 to 10

-----

49.9

-----

1 to 5

100 K

124

-----

0 to 20

-----

-------

24.9

 

 

 

 

"-----" means "Resistor must not be installed"

R18

R29

E F Jumpers E and F : Closed only if the output is 4 to 20 mA.

Replace or add the indicated resistors with the values shown in Tables 2 and 3 for the desired output.

R30

FIG.6

R24

R25

R31

R32

5

 

 

 

 

Page 6
Image 6
Omega Vehicle Security CCT-80 Series manual Changing the Signal Output, NON Standard Output Voltages Currents