6-2SectionProgramming Console Operations
98
3. Press the CLR Key to end binary monitoring and return to the normal moni-
toring display.
CLR c010
0000
6-2-15 Three-Word MonitorThis operation is used to monitor the status of three consecutive words. It is
possible in any mode.
RUN MONITOR PROGRAM
OK OK OK
1, 2, 3... 1. Monitor the status of the first of the three words according to the procedure
described in 6-2-12 Bit, Digit, Word Monitor.
If 2 or more words are being monitored, the desired first word should be left-
most on the display.
(Word monitor)
c200
89AB
2. Press the EXT Key to begin 3-word monitoring. The status of the selected
word and the next two words will be displayed, as shown below. In this case,
DM 0000 was selected.
EXT c202 c201 c200
0123 4567 89AB
The Up and Down Arrow Keys can be used to shift one address up or down.
The status of the displayed words can be changed at this point. Refer to
6-2-18 Three-word Data Modification.
The display can be changed to display ASCII text, which is useful when
three consecutive words containing an ASCII message are displayed. Refer
to 6-2-26 Hex-ASCII Display Change.
3. Press the CLR Key to end 3-word monitoring and return to the normal moni-
toring display. The rightmost word on the 3-word monitor display will be
monitored.
CLR c200
89AB
Note The operating mode can be changed without altering the current monitor display
by holding down the SHIFT Key and then changing the operating mode.
6-2-16 Signed Decimal MonitorThis operation converts the contents of the specified word from signed hexa-
decimal (two’s complement format) to signed decimal for display. The opera-
tion can be executed while using I/O monitoring, multiple address monitoring
or 3-word monitoring.
RUN MONITOR PROGRAM
OK OK OK
1, 2, 3... 1. Monitor the word that is to be used for decimal monitor with sign. During mul-
tiple address monitoring, the leftmost word will be converted.
(Multiple address monitor)
c200 cL0020000
FFF0 0000^ OFF
2. Press the SHIFT+TR Keys to display the leftmost word as signed decimal.
SHIFT TR c200
Ć00016