Fire alarm systems

Fire alarm systems

Combination heat

detector 4318

Conventional heat detector

Rate-of-rise and fixed temperature alarm levels

General

Heat detector 4318 is a conventional com- bination heat detector, class A1R. It "gives an alarm" at a certain fixed temperature (59°C) and/or at a certain temperature rise, "rate-of-rise" function.

The sensing element is a thermistor.

The detector is plugged in a conventional base 2324 connected to a conventional zone line input.

The base has an LED that will light when the detector goes into alarm. In the base there are terminals to connect an external LED, e.g. 2218.

Environment friendly

The detector has unleaded soldering. The latest IC technology reduces the number of semiconductors and other electronic components to a minimum.

Product applications

This conventional heat detector can be used in the systems EBL500 / 512 / 128 / 1000 / 2000.

The detector is intended for indoor use and in dry premises.

Heat detectors are normally used in small rooms where the temperature can be expected to rise rapidly in case of a fire or places where smoke detectors can not be used.

Panasonic Electric Works Fire & Security Technology Europe AB Jungmansgatan 12, SE-211 19 Malmö, Sweden

Tel: +46 (0)40 697 70 00 • Fax: +46 (0)40 697 70 99 info-fste@eu.pewg.panasonic.comwww.panasonic-fire-security.com

Page 1