Panasonic C14RS, E32RS FP0 Thermocouple Input Expansion Units, FP0-TC4 and FP0-TC8 specifications

Models: E32P E32RS E8RS E16T FP0-C16T C32T C32P FP0-C10RS E16RS C16CT C14RS C14CRS E16P E32T T32CT FP0T32CP C32CP C16P C32CT C10CRS C16CP

1 28
Download 28 pages 325 b
Page 15
Image 15

FP0 Thermocouple Input Expansion Units

Enable High Precision Tempera ture Control a t Low Cost

The FP0-TC4 and FP0-TC8 thermocouple units are suitable for user-friendly temperature acquisition using standard thermocouples with

high precision.

Up to three units can be added to each control unit, enabling temperature control of up to 24 channels.

The temperature data obtained using the thermocouple is converted to the digital value to be read into the FP0 control unit.

Standard types of thermocouples can be used: K, J, T and R

3 temperature measurement ranges are available: -100°C to +500°C (thermocouple types: K and J) -100°C to +400°C (thermocouple type : T)

- 0°C to +1500°C (thermocouple type : R)

The temperature data measured using the sensor is converted to degrees Celsius or degrees Fahrenheit inside the thermocouple unit.

The converted data (°C or °F) is averaged, so that even unstable input signals can be properly read.

Broken thermocouples can be detected.

Temperature control

FP0-TC8

FP0-TC4

8 channels

4 channels

FP0-TC4 and FP0-TC8 specifications

Item

 

Specification

 

Input points

Up to 8 channels per unit (The number of input points can be changed 2, 4, 6 and 8 channels are available)

 

Thermocouple types K, J

 

 

-100°C to 500°C

Input range

Thermocouple types T

 

 

-100°C to 400°C

 

 

 

 

 

 

Thermocouple types R

 

 

0°C to 1500°C

Resolution

 

 

0.1°C

 

 

 

300ms: when using 2 channels for an input points

 

Sampling cycle

 

500ms: when using 4 channels for an input points

 

 

700ms: when using 6 channels for an input points

 

 

 

900ms: when using 8 channels for an input points

 

 

 

Range for K and J

 

(-100°C to 500°C):

0.8°C

Accuracy

 

Range for T

 

(-100°C to 400°C):

0.8°C

 

Range for R

 

(0°C to 99.9°C):

3°C

 

 

 

 

(100°C to 299.9°C):

2.5°C

 

 

 

 

(300°C to 1500°C):

2°C

Input Impedance

 

More than 1MΩ

 

Insulation method

- Between thermocouple input terminals and control unit internal circuits Photo-coupler insulation/DC-DC insulation

- Between thermocouple input terminal channels PhotoMOS relay insulation

 

 

 

 

 

 

07/2007

15

 

Page 15
Image 15
Panasonic C14RS, FP0T32CP FP0 Thermocouple Input Expansion Units, Enable High Precision Tempera ture Control a t Low Cost