FPΣ (Sigma)
Specification tables
I N P U T S P E C I F I C AT I O N S
| Insulation method |
| Optical coupler |
|
| Rated input voltage |
| 24VDC |
|
| Input voltage range |
| 21.6 to 26.4VDC |
|
| Rated input current |
| 3.5mA - 8mA depends on input no. |
|
|
|
| 8 points/common | |
| Input points per common | 32 points/common | ||
|
|
| negative of input power supply can be connected to terminal | |
| Min. ON voltage / Max. OFF current | 19.2V / 3mA - 6mA depends on input no. | ||
| Max. ON voltage / Min. OFF current | 2.4V / 1.3mA |
| |
| Input impedance |
| 3k - 6.8k depends on input no. |
|
| Response time | CPU: | 1ms or less, 5µs (HSC, pulse catch, interrupt input) | |
|
| Expansion: | 0.2ms (OFF |
|
|
|
| 0.3ms (ON |
|
| Operating indicator |
| LED |
|
|
|
|
| |
| O U T P U T S P E C I F I C AT I O N S | - T R A N S I S T O R O U T P U T T Y P E | ||
| Item |
| ||
| Insulation method |
| Optical coupler |
|
| Output method |
| Open collector |
|
| Rated voltage range |
| 5 to 24VDC | 24VDC |
| Operating load voltage range | 4.75 to 26.4VDC | 21.6 to 26.4VDC | |
| Max. load current |
| For Y0, Y1, Y3, Y4: 0.3A | For Y0, Y1, Y3, Y4: 0.5A |
|
| For Y2, Y5 to YF: 0.1A | For Y2, Y5 to YB: 0.3A | |
|
|
| ||
| Max. surge current |
| For Y0, Y1, Y3, Y4: 0.9A | For Y0, Y1, Y3, Y4: 1.5A |
|
| For Y2, Y5 to YF: 0.5A | For Y2, Y5 to YB: 0.7A | |
|
|
| ||
| Output points per common | 16 points/common | 12 points/common | |
|
| OFF | For Y0, Y1, Y3, Y4 at 15mA or lesss: <2µs | |
| Response time |
| For Y2, Y5 and higher: < 0.2ms |
|
| ON | For Y0, Y1, Y3, Y4 at 15mA or lesss: <8µs | ||
|
| |||
|
| For Y2, Y5 and higher: < 0.5ms |
| |
|
|
|
| |
| Power supply for driving internal circuit | none |
| |
| Operating indicator |
| LED |
|
| Phase fault protection |
| Thermal protection for Y2, Y5 and higher | |
|
|
|
| |
| O U T P U T S P E C I F I C AT I O N S | - R E L AY O U T P U T T Y P E |
| |
| Output type |
| Normally open (1 Form A) |
|
| Rated control capacity |
| 2A 250VAC, 2A 30VDC (max. 4.5A/common)(resistive load) | |
| Output points per common | 8 points/ common |
| |
| Response time | OFF | 10ms or less |
|
| ON | 8ms or less |
| |
|
|
| ||
| Mechanical life time |
| 20 million operations or more |
|
| Electrical life time |
| 100.000 operations or more |
|
| Surge absorber |
| 21.6 to 26.4VDC (70mA) |
|
| Operating indicator |
| LED |
|
G E N E R A L S P E C I F I C AT I O N S
Rated operating voltage | 24VDC |
Operating voltage range | 21.6 to 26.4VDC |
Allowable no voltage time | 4ms (at 21.6V), 10ms (at 26.4V) |
Ambient temperature | 0°C to +55°C |
Storage temperature | |
Ambient humidity | 30 to 85% RH |
Storage humidity | 30 to 85% RH |
Vibration resistance | 10 to 55Hz, 1 cycle/min., |
| double amplitude of 0.75mm, |
| 10min. on 3 axes |
|
|
Shock resistance | 98m/s2 or more, |
| 4 times on 3 axes |
|
|
Noise humidity | 1,000V |
| widths 50ns and 1µs |
|
|
Operating condition | free from corrosive gasses |
| and excessive dust |
|
|
18 | 02/2006 |