Parker Products WCS-SIF-01 manual Installation & Setup Instructions, Open Close

Models: WCS-SIF-01

1 20
Download 20 pages 35.79 Kb
Page 5
Image 5

WCS-SIF-01

Training & Maintenance Manual

Installation & Setup Instructions

Setup

Below are the step by step setup procedures for properly setting the flow control and feedback sensor.

How to Set the Flow Control Properly

Begin by turning the flow control clockwise until it stops. If this is done properly, then the weld stroke should move extremely slow or not at all.

Note: As stated in the Installation procedure, the pre-stroke valve must be actuated prior to the weld stroke valve in order for the weld cylinder to move correctly.

Slowly (1/4 to 1/2 turn at a time) begin to open the flow control by turning counterclockwise. The weld tips should now close upon actuation of the valves. At this point, you should begin to hear a second exhaust coming from the weld unit once the weld tips have made contact. This second exhaust is the air from the front side of the cylinder bypassing the flow control. As you continue to speed up the weld stroke by turning the flow control, the delay between the tips closing and the second exhaust will get shorter. Also, check the feedback sensor while this is occurring. The indicator light from the sensor should illuminate when you hear the second exhaust. This is the key to determining the proper setting of the flow control. The optimum setting for each weld block will be different for each gun, based on the bore size and weld stroke used. Continue to open the flow control, allowing the weld tips to close faster until:

1.You have reached an impact speed you are happy with.

2.You have reached an acceptable decibel noise level.

3.You see that the second exhaust and feedback sensor illumination occur “just” as the weld tips contact.

Open

Close

Flow Control

Flow Control

5mm

Allen Wrench Required For Flow Control Adjustment

Electrical Changes (Sample):

GUN PR

CUT CA RE-WEL

TEACHI

K2 STR

WELD R

 

ESS

BLE CH D(PB)

NG

OKE CH

EADY S

 

 

ECKING

 

 

ANGE

ENSOR

 

M005

M052

M03C

P1-M00F

P1-M00F

X024

1022 WELD START

Note: This is a judgement call. If the flow control is set

00061

too far open, then the weld block could result in welding misfire causing the gun to fire before the weld tips close fully. The reason this would occur is because the flow control has been opened so much that all the air on the front side of the cylinder has exhausted before the tips fully close, thus negating the “low impact” benefit of the system. To guarantee proper performance, find the setting where the exhaust / illumination occurs “just” as the tips close, and then adjust the flow control 1/2 turn clockwise.

GUN PR CUT CA RE-WEL

RE-WEL CHECK

TEACHI

STROKE

ESS

BLE CH D(PB)

D(PB)

MODE/P

NG

CHANG

 

ECKING

 

ROGRAM

 

E TIME

M005

M052 M00B

M03C

P1-L04B

P1-M00F

T015

 

 

AUTO R

MANUAL

 

 

 

 

E-WELD

WELD

 

 

 

 

M05B

P1-L058

 

Insert contact on the

 

 

 

 

 

 

 

 

 

 

WELD START rung of

 

RE-WEL

 

 

 

the Robot PLC program.

 

D

 

 

 

 

 

M00B

 

 

 

 

How to Set the Feedback Sensor Properly

The purpose of the feedback sensor is to provide an input signal at the exact moment that full weld pressure has been obtained at the weld tips. Traditionally this is achieved using squeeze time. An experienced weld / electrical engineer is needed to place the feedback sensor input into the PLC program. The location of this input will vary depending on the PLC manufacturer. Consult the robot manufacturer for the proper input location.

Above is a sample PLC program where the feedback sensor was placed during a typical install. The location of the input should be right before the weld start command. Once the input has been placed into the program, disconnect the sensor cable from the feedback sensor. This will allow you to determine whether or not the input was placed in the correct spot.

Perform a trial run. If on the first weld, the weld tips close and the robot stops, then the sensor input has been located correctly in the program. If the robot continues to run, despite the cable being disconnected, then the sensor input is not correct. Review the location and then try the trial run again.

Note: The weld block should perform the same whether the robot is in manual or automatic mode.

Pneumatic

Parker Hannifin Corporation Pneumatic Division Richland, Michigan www.parker.com/pneumatics

Page 5
Image 5
Parker  Products WCS-SIF-01 manual Installation & Setup Instructions, How to Set the Flow Control Properly, Open Close