Modu-Fire®Gas-Fired Boiler

By Installer

Remote Gas

Shutoff (not

supplied)

 

Union

Drip Leg

 

 

 

 

Shutoff (on

 

 

boiler)

 

 

Gas Meter (not

 

 

supplied)

Gas Piping

Installation

on the boiler. Gas piping should be installed in accor- dance with National Fuel Gas Code, ANSI Z223.1, latest edition, and any other local codes which may apply; in Canada see CAN/CGA-B 149.

Note: See chart below for required pipe size, based on overall length of pipe from meter plus equivalent length of all fittings. Approximate sizing may be based on 1 cubic foot of natural gas per 1,000 Btu per hour input, i.e., 900,000 Btu per hour requires about 900 cubic feet per hour. (See Typical Boiler Operating Conditions, Section 4.3, for more information.)

WARNING!

All threaded connections must be made using a pipe compound that is resistant to the action of liquefied petroleum gases. Do not use Teflon tape on gas line threads.

Note: Install a sediment trap (drip leg) and a union connection ahead of the primary manual shutoff valve

Pipe Capacity for Natural Gas

Nominal

 

Equivalent Pipe Length

Maximum Capacity in Cubic Feet of Natural Gas per Hour

Iron

Internal

 

 

Pressure Drop of 0.5 inch Water Column/Equivalent Length of

Pipe

Diameter

 

 

 

 

 

Pipe (in feet)

 

 

 

Size

(Inches)

90º Ell

Tee

 

 

 

 

 

 

 

 

 

(Inches)

 

(Feet)

(Feet)

20

40

60

 

80

 

100

150

200

1-1/4

1.380

3.45

6.9

950

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1-1/2

1.610

4.02

8.04

1,460

990

810

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

2.067

5.17

10.3

2,750

1,900

1,520

 

1,300

 

1,150

950

800

 

 

 

 

 

 

 

 

 

 

 

 

 

2-1/2

2.469

6.16

12.3

4,350

3,000

2,400

 

2,050

 

1,850

1,500

1,280

 

 

 

 

 

 

 

 

 

 

 

 

 

3

3.068

7.67

15.3

7,700

5,300

4,300

 

3,700

 

3,250

2,650

2,280

4

4.026

10.1

20.2

15,800

10,900

8,800

 

7,500

 

6,700

5,500

4,600

10

Page 13